The measure is not done during the first cycle after the power-up, or if the position request signal changes during the
measuring time.
The above warning condition is signalled only by the red LED (alarm/warning) located on the local operator
interface.
4.2.10.
Motor/pump control
The motor of the hydraulic pump is controlled by the MCU. The following operating mode can be configured
via
local operator interface:
1)
OFF:
electrical motor always off
2)
ON:
electrical motor always on
3)
AUTO:
- in LOCAL the electrical motor is always running
- in OFF the power of the electrical motor is switched off in 30 sec. It is switched on when the local selector is
moved to LOCAL or REMOTE
- in REMOTE the electrical motor switches off, if the variation of the position request signal is less than 0.5%
for 15 min. It is switched on if the position request signal changes or if the pressure switch contact opens
If the pressure switch is still open after 10 min. from the start of the motor pump, an alarm is generated
(HYDRAULIC PUMP)
4.2.11.
Language selection
To visualise the messages of the display the operator can choose between two available languages (Italian and
English).
4.2.12.
Maintenance instruction
A large amount of data is stored in the MCU memory and it is available for future analysis or to assist the operator
in the maintenance program. The maintenance menu includes the set password routine, to read the maintenance date
operation, to clear recent data log and to set the next maintenance date.