FRONT VIEW

SIDE VIEW

2-1/8"

(54,0 mm)

 

2-1/16"

(52,4 mm)

1"

(25,4 mm)

5/8"

(15,9 mm)

1-1/32"

(26,2 mm)

1/2" NPT

WRENCH

FLAT

7/16" 

(11,1 mm)

MAKE-IN

ELEVATION VIEW

TOP OF SPRINKLER

DEFLECTOR

TOWARDS WINDOW

Figure 1 - Model WS, Horizontal Sidewall

Specific Application Window Sprinkler

Figure 2 - Model WS, Pendent Vertical Sidewall

Specific Application Window Sprinkler

Figure 3 - Cross Section Model WS, Pendent Vertical Sidewall

Specific Application Window Sprinkler

1-5/8"

(41,3 mm)

  2-1/8 "

(54,0 mm)

13/16"

(20,6 mm)

WRENCH

FLAT

1/2" NPT

TOP OF SPRINKLER

DEFLECTOR

7/16" (11,1 mm)

MAKE-IN

ELEVATION

VIEW

TOWARDS WINDOW

SPRINKLER

FRAME

DEFLECTOR

GLASS BULB

OPERATING 

ELEMENT

GASKETED SPRING 

PLATE

(BELLEVILLE 

SEAL)

BUTTON 

ASSEMBLY

COMPRESSION

SCREW

OBSOLETE

Содержание CENTRAL WS

Страница 1: ...are the first sprinklers ever to be specifically Listed to provide protection for heat strengthened or tempered glass windows using closed sprinklers As part of the testing the gas flow required to ac...

Страница 2: ...um Distance from Vertical Mullion 4 101 6 mm Ref Figure D Intermediate Horizontal Mullions Intermediate Horizontal Mullions were not tested with the window sprinkler Their use is outside the scope of...

Страница 3: ...Figure 2 Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler Figure 3 Cross Section Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler 1 5 8 41 3 mm 2 1 8 54...

Страница 4: ...21 ft lbs 28 5 Nm of torque is to be used to install 1 2 inch NPT sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leakage or impair ment of the sprinkler Step 1 The...

Страница 5: ...x 4 1 22 m Min 4 101 6 mm Butt Joint No Minimum or Maximum Mullion Window Sprinklers are NOT required to be located with respect to horizontal or vertical butt joints 8 2 44 m Maximum 6 1 83 m Minimum...

Страница 6: ...e shipped or stored where their tem peratures will exceed 100 F 38 C and they must never be painted plated coated or otherwise altered after leaving the factory Modified sprinklers must be replaced Sp...

Страница 7: ...dified or repaired in accordance with applicable Standards of the National Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found by Tyco Fire Pr...

Страница 8: ...Products Figure H Recessed Ceiling Condition Pendent Vertical and Horizontal Sidewall Window Sprinklers can be installed into recessed ceiling spaces Curtains blinds or other window coverings are NOT...