background image

Figure F

WS™ Horizontal Sidewall

Installation Note:

All frame arms must

be in vertical alignment

Window

Frame

Maximum

Height 13'

(3,96 m)

No Maximum

Height

No Maximum

Distance

Window 

Sprinklers

Shown on one 

side for clarity.

All combustible materials

shall be kept 2" (50,8 mm) 

from the front face of the 

glass.  This can be 
accomplished by a 

36" (914,4 mm) pony wall 

or any other method 

acceptable to the Authority 

Having Jurisdiction.

1/2" (12,7 mm) to 4" (101,6 mm)

Must be within the Mullion of the 

Window.

2" (50,8 mm)

±

1" (25,4 mm)

"TOP"

The Model WS Specific Application
Window Sprinklers must be main-
tained and serviced in accordance
with the following instructions.

NOTES

Before closing a fire protection system
main control valve for maintenance
work on the fire protection system it
controls, permission to shut down the
affected fire protection systems must
be obtained from the proper authori-
ties.  All personnel who may be
affected by this action must be
notified.

Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.

Automatic sprinklers must never be
shipped or stored where their tem-
peratures will exceed 100

°

F/38

°

C and

they must never be painted, plated,
coated or otherwise altered after
leaving the factory. Modified sprinklers
must be replaced. Sprinklers that
have been exposed to corrosive
products of combustion, but have not
operated, should be replaced if they
cannot be completely cleaned by
wiping the sprinkler with a cloth or by
brushing it with a soft bristle brush.

Care must be exercised to avoid
damage - before, during, and after
installation. Sprinklers damaged by
dropping, striking, wrench twist/
slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has
lost liquid from its bulb (ref. Installa-
tion Section).

The owner is responsible for the
inspection, testing, and maintenance
of their fire protection system and
devices in compliance with this
document, as well as with the appli-
cable standards of the National Fire
Protection Association (e.g., NFPA
25), in addition to the standards of any
other authorities having jurisdiction.
The installing contractor or sprinkler
manufacturer should be contacted
relative to any questions.

It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Care &
Maintenance

OBSOLETE

Содержание CENTRAL WS

Страница 1: ...are the first sprinklers ever to be specifically Listed to provide protection for heat strengthened or tempered glass windows using closed sprinklers As part of the testing the gas flow required to ac...

Страница 2: ...um Distance from Vertical Mullion 4 101 6 mm Ref Figure D Intermediate Horizontal Mullions Intermediate Horizontal Mullions were not tested with the window sprinkler Their use is outside the scope of...

Страница 3: ...Figure 2 Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler Figure 3 Cross Section Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler 1 5 8 41 3 mm 2 1 8 54...

Страница 4: ...21 ft lbs 28 5 Nm of torque is to be used to install 1 2 inch NPT sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leakage or impair ment of the sprinkler Step 1 The...

Страница 5: ...x 4 1 22 m Min 4 101 6 mm Butt Joint No Minimum or Maximum Mullion Window Sprinklers are NOT required to be located with respect to horizontal or vertical butt joints 8 2 44 m Maximum 6 1 83 m Minimum...

Страница 6: ...e shipped or stored where their tem peratures will exceed 100 F 38 C and they must never be painted plated coated or otherwise altered after leaving the factory Modified sprinklers must be replaced Sp...

Страница 7: ...dified or repaired in accordance with applicable Standards of the National Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found by Tyco Fire Pr...

Страница 8: ...Products Figure H Recessed Ceiling Condition Pendent Vertical and Horizontal Sidewall Window Sprinklers can be installed into recessed ceiling spaces Curtains blinds or other window coverings are NOT...

Отзывы: