Figure A - Interior Fire Separation

When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a fire separation provided in an interior fire
separation, the window sprinklers are installed on both sides of the window in the fire
separation.

Figure B - Exterior Separation

EXPOSURE

SIDE

OUTSIDE

INSIDE

When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a fire separation provided in jurisdictions
where exterior spatial separation is defined as protecting an adjacent building from a fire in
your building, window sprinklers are installed on the interior side of the building

Installation

The Model WS Specific Application
Window Sprinklers must be installed
in accordance with the following
instructions.

NOTES

Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontal, a small air bubble
should be present. The diameter of
the air bubble is approximately 1/16
inch (1,6 mm).

A leak tight 1/2 inch NPT sprinkler
joint should be obtained with a torque
of 7 to 14 ft.lbs. (9,5 to 14,0 Nm).  A
maximum of 21 ft.lbs. (28,5 Nm) of
torque is to be used to install 1/2 inch
NPT sprinklers. Higher levels of
torque may distort the sprinkler inlet
with consequent leakage or impair-
ment of the sprinkler.

Step 1. The pendent vertical sidewall
sprinkler must be installed only in the
pendent position with the centerline of
the sprinkler parallel to the glass
surface.  The sprinkler must be
oreintated so that the direction of flow
indicated on the sprinkler deflector is
facing the window.  The horizontal
sidewall sprinker must be installed
only in the  horizontal position with the
centerline of the sprinkler perpendicu-
lar to the glass surface. The sprinkler
must be oreintated so that the word
"Top"  indicated on the sprinkler
deflector is facing the top of window
frame.

Step 2. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.

Step 3. Wrench tighten the Sprinkler
using only the Combination Sprinkler
Wrench (Ref. Figure 4).   The Combi-
nation Sprinkler Wrench is to be
applied to the Sprinkler Wrench flats
only.

Figure 4 - Combination Sprinkler Wrench (Part #1106)

Figure C - Exterior Separation

When acceptable to the Authority Having Jurisdiction the Model WS Specific Application
Window Sprinklers may be used in either a sprinklered or unsprinklered building to protect
nonoperable window openings that are part of a fire separation provided in jurisdictions
where exterior spatial separation is defined as protecting your building from a fire in an
adjacent building, open window sprinklers are installed on the exterior side of the building

EXPOSURE

SIDE

INSIDE

OUTSIDE

OBSOLETE

Содержание CENTRAL WS

Страница 1: ...are the first sprinklers ever to be specifically Listed to provide protection for heat strengthened or tempered glass windows using closed sprinklers As part of the testing the gas flow required to ac...

Страница 2: ...um Distance from Vertical Mullion 4 101 6 mm Ref Figure D Intermediate Horizontal Mullions Intermediate Horizontal Mullions were not tested with the window sprinkler Their use is outside the scope of...

Страница 3: ...Figure 2 Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler Figure 3 Cross Section Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler 1 5 8 41 3 mm 2 1 8 54...

Страница 4: ...21 ft lbs 28 5 Nm of torque is to be used to install 1 2 inch NPT sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leakage or impair ment of the sprinkler Step 1 The...

Страница 5: ...x 4 1 22 m Min 4 101 6 mm Butt Joint No Minimum or Maximum Mullion Window Sprinklers are NOT required to be located with respect to horizontal or vertical butt joints 8 2 44 m Maximum 6 1 83 m Minimum...

Страница 6: ...e shipped or stored where their tem peratures will exceed 100 F 38 C and they must never be painted plated coated or otherwise altered after leaving the factory Modified sprinklers must be replaced Sp...

Страница 7: ...dified or repaired in accordance with applicable Standards of the National Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found by Tyco Fire Pr...

Страница 8: ...Products Figure H Recessed Ceiling Condition Pendent Vertical and Horizontal Sidewall Window Sprinklers can be installed into recessed ceiling spaces Curtains blinds or other window coverings are NOT...