background image

Figure D - Multiple Windows Separated by Mullions

Figure F - Windows with Horizontal Mullions

Figure E - Multiple Windows Separated by Butt Joints

Mullion

Intermediate Mullion

Window Sprinklers are NOT Listed to protect windows

when intermediate horizontal mullions are present.

(Pendent Vertical Sidewall Sprinklers show for clarity)

Max - 4' (1,22 m)
Min  - 4" (101,6 mm)

Butt Joint

No Minimum

or Maximum 

Mullion

Window Sprinklers are NOT required to be

located with respect to horizontal or vertical butt joints. 

 

8' (2,44 m)

Maximum

  6' (1,83 m)

Minimum

(Pendent Vertical Sidewall Sprinklers show for clarity)

8' (2,44 m)

Maximum

Max - 4' (1,22 m)
Min  - 4" (101,6 mm)

Mullion

 6' (1,83 m)

Minimum*

*Minimum Distance Between 
Window Sprinklers is 6' (1,83 m) 
unless separated by a baffle or 
mullion of sufficiant depth to act 
as a baffle. 

(Pendent Vertical Sidewall Sprinklers show for clarity)

OBSOLETE

Содержание CENTRAL WS

Страница 1: ...are the first sprinklers ever to be specifically Listed to provide protection for heat strengthened or tempered glass windows using closed sprinklers As part of the testing the gas flow required to ac...

Страница 2: ...um Distance from Vertical Mullion 4 101 6 mm Ref Figure D Intermediate Horizontal Mullions Intermediate Horizontal Mullions were not tested with the window sprinkler Their use is outside the scope of...

Страница 3: ...Figure 2 Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler Figure 3 Cross Section Model WS Pendent Vertical Sidewall Specific Application Window Sprinkler 1 5 8 41 3 mm 2 1 8 54...

Страница 4: ...21 ft lbs 28 5 Nm of torque is to be used to install 1 2 inch NPT sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leakage or impair ment of the sprinkler Step 1 The...

Страница 5: ...x 4 1 22 m Min 4 101 6 mm Butt Joint No Minimum or Maximum Mullion Window Sprinklers are NOT required to be located with respect to horizontal or vertical butt joints 8 2 44 m Maximum 6 1 83 m Minimum...

Страница 6: ...e shipped or stored where their tem peratures will exceed 100 F 38 C and they must never be painted plated coated or otherwise altered after leaving the factory Modified sprinklers must be replaced Sp...

Страница 7: ...dified or repaired in accordance with applicable Standards of the National Fire Protection Association and or the standards of any other Authorities Having Jurisdiction Materials found by Tyco Fire Pr...

Страница 8: ...Products Figure H Recessed Ceiling Condition Pendent Vertical and Horizontal Sidewall Window Sprinklers can be installed into recessed ceiling spaces Curtains blinds or other window coverings are NOT...

Отзывы: