background image

Care and
Maintenance

The Series RFII must be maintained
and serviced in accordance with the
following instructions:

NOTES

Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
When properly installed, there is a
nominal 3/32 inch (2,4 mm) air gap
between the lip of the Cover Plate and
the ceiling, as shown in Figure 2. This
air gap is necessary for proper opera-
tion of the sprinkler. If the ceiling is to
be repainted after the installation of
the Sprinkler, care must be exercised
to ensure that the new paint does NOT
seal off any of the air gap.
Factory painted Cover Plates MUST
NOT be repainted. They should be re-
placed, if necessary, by factory
painted units.
Do not pull the Cover Plate relative to
the Enclosure. Separation may result.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must  never be
shipped or stored where their tempera-
ture will exceed 100°F/38°C and they
must never be painted, plated, coated
or otherwise altered after leaving the
factory. Modified sprinklers must be re-
placed. Sprinklers that have been ex-
posed to corrosive products of com-
bustion, but have not operated, should
be  replaced  if  they cannot  be  com-
pletely cleaned by wiping the sprinkler
with a cloth or by brushing it with a soft
bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed, do not
reinstall it  or a  replacement  without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it im-
mediately.

The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in  compliance with this  docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
spr inkler systems be inspected,
tested, and maintained by a qualified
Inspection Service.

Limited
Warranty

Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty

is

given

for

products

or

components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products’ sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer’s representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS’ LI-
ABILITY EXCEED   AN   AMOUNT
EQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.

Ordering
Procedure

When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability.

Sprinkler Assembly:

Specify: TY3532, (specify temperature
rating) Series RFII Concealed Pen-
dent Sprinkler, P/N (specify).

155F/68C

200F/93C

TY3532

51-794-1-155

51-794-1-200

Separately Ordered Cover Plate:

Specify: (specify temperature rating)
Series RFII  Concealed Cover Plate
with (specify finish), P/N (specify).

135F/57C*

165F/74C**

Brass

56-792-1-135

56-792-1-165

Bright Brass

56-792-2-135

56-792-2-165

Chrome

56-792-9-135

56-792-9-165

Brushed Chrome

56-792-8-135

56-792-8-165

White

56-792-0-135

56-792-0-165

Bright White

56-792-4-135

56-792-4-165

Off White

56-792-5-135

56-792-5-165

Black

56-792-6-135

56-792-6-165

Custom

56-792-X-135

56-792-X-165

* For use with 155F/68C sprinklers.
** For use with 200F/93C sprinklers.

Sprinkler Wrench:

Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.

Page 4 of 4

TFP260

TYCO FIRE PRODUCTS

, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

OBSOLETE

Содержание CENTRAL RFII Series

Страница 1: ...ct against the Protective Cap When the ceiling in stallation is complete the Protective Cap is removed and the Cover Plate Assembly installed WARNINGS The Series RFII Concealed Pendent Sprinklers described herein must be installed and maintained in compli ance with this document as well as with the applicable standards of the National Fire Protection Association in addition to the standards of any...

Страница 2: ...e obtained with a torque of 7 to 14 ft lbs 9 5 to 19 0 Nm A maxi mum of 21 ft lbs 28 5 Nm of torque is to be used to install sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leak age or impairment of the sprinkler Do not attempt to compensate for in sufficient adjustment in the Sprinkler Assembly by under or over tightening the Sprinkler Support Cup Assembly Readj...

Страница 3: ...ntil its flange just comes in contact with the ceiling Do not continue to screw on the Cover Plate Retainer Assembly such that it lifts a ceiling panel out of its normal position If the Cover Plate Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate Re tainer Assembly cannot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned TFP260 Pag...

Страница 4: ...ntained by a qualified Inspection Service Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date of ship ment by Tyco Fire Products No war ranty is given for ...

Отзывы: