background image

Operation

When exposed to heat from a fire, the
Cover Plate, which is normally sol-
dered to the Retainer at three points,
falls away to expose the Sprinkler As-
sembly. At this point the Deflector sup-
ported by the Guide Pins drops down
to its operational position.
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing water to flow.

Design
Criteria

The RFII (TY3532) Concealed Pen-
dent Sprinklers are UL and C-UL
Listed for use in light hazard occupan-
cies, using the design criteria in Table
A, in addition to the requirements
specified in the current NFPA 13 for
extended coverage pendent sprin-
klers.
The Series RFII Concealed Pendent
Sprinklers are only listed and ap-
proved with the Series RFII Concealed
Cover Plates having a metallic or white
painted finish.
The Series RFII must not be used in
applications where the air pressure
above the ceiling is greater than that
below. Down drafts through the Sup-
port Cup could delay sprinkler opera-
tion in a fire situation.

Installation

The Series RFII must be installed in
accordance with the following instruc-
tions:

NOTES

Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/68°C and 3/32
inch (2,4 mm) for the 200°F/93°C tem-
perature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under- or over-tightening

the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.

Step 1.

The sprinkler must only be

installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.

Step 2.

Remove the Protective Cap.

Step 3.

With pipe thread sealant ap-

plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.

Step 4.

Wrench tighten the sprinkler

using only the RFII Sprinkler Wrench
(Ref. Figure 3). The RFII Sprinkler
Wrench is to be applied to the Sprin-
kler as shown in Figure 3.

Step 5.

Replace the Protective Cap

(Ref. Figure 4) by pushing it upwards

Page 2 of 4

TFP260

FIGURE 1

SERIES RFII CONCEALED SPRINKLER

ASSEMBLY

GUIDE

DEFLECTOR

RETAINER

WITH THREAD

DIMPLES

(DROPPED

POSITION)

PINS (2)

SPRING

EJECTION

TABS (3)

SOLDER

DEFLECTOR

ROLL FORMED

THREADS

CUP WITH

SUPPORT

FRAME

1/2" NPT

SPRINKLER/SUPPORT CUP

ASSEMBLY

COVER PLATE/RETAINER

ASSEMBLY

COVER

PLATE

THREAD INTO

UNTIL MOUNTING

SUPPORT CUP

SURFACE IS

FLUSH WITH

CEILING

SCREW

COMPRESSION

CAP

BULB

SEALING

ASSEMBLY

* Registered Trademark of DuPont

TABLE A

SERIES RFII (TY3532)

155F/68C AND 200F/93C CONCEALED SPRINKLER

HYDRAULIC DESIGN CRITERIA

RESPONSE

RATING

QUICK

QUICK

STANDARD

SPACING

MINIMUM

FLOW/PRESSURE

16’ x 16’

(4,9 m x 4,9 m)

18’ x 18’

(5,5 m x 5,5 m)

20’ x 20’

(6,1 m x 6,1 m)

26.0 GPM / 21.6 PSI

(98,4 LPM / 1,49 BAR)

33.0 GPM / 34.7 PSI

(124,9 LPM / 2,39 BAR)

40.0 GPM / 51.0 PSI

(151,4 LPM / 3,52 BAR)

OBSOLETE

Содержание CENTRAL RFII Series

Страница 1: ...ct against the Protective Cap When the ceiling in stallation is complete the Protective Cap is removed and the Cover Plate Assembly installed WARNINGS The Series RFII Concealed Pendent Sprinklers described herein must be installed and maintained in compli ance with this document as well as with the applicable standards of the National Fire Protection Association in addition to the standards of any...

Страница 2: ...e obtained with a torque of 7 to 14 ft lbs 9 5 to 19 0 Nm A maxi mum of 21 ft lbs 28 5 Nm of torque is to be used to install sprinklers Higher levels of torque may distort the sprinkler inlet with consequent leak age or impairment of the sprinkler Do not attempt to compensate for in sufficient adjustment in the Sprinkler Assembly by under or over tightening the Sprinkler Support Cup Assembly Readj...

Страница 3: ...ntil its flange just comes in contact with the ceiling Do not continue to screw on the Cover Plate Retainer Assembly such that it lifts a ceiling panel out of its normal position If the Cover Plate Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate Re tainer Assembly cannot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned TFP260 Pag...

Страница 4: ...ntained by a qualified Inspection Service Limited Warranty Products manufactured by Tyco Fire Products are warranted solely to the original Buyer for ten 10 years against defects in material and work manship when paid for and properly installed and maintained under normal use and service This warranty will ex pire ten 10 years from date of ship ment by Tyco Fire Products No war ranty is given for ...

Отзывы: