PLUMB-IN LP GAS INSTALLATION
(LP SYSTEM)
–
P
INNACLE
G
AS
G
RILL
The installation must conform with local codes or, in the absence of local codes, with either
the national Fuel Gas Code, ANSI Z223.1/NFPA 54, or CAN/CGA-B149.1, Natural Gas Installation
Code or CAN/CGA-B149.2, Propane Installation Code.
1.
This gas appliance and its individual shutoff valve must be disconnected from the gas supply
piping system during any pressure testing of that system at the test pressures in excess of 1/2
psi (3.5 kPa).
2.
This appliance must be isolated from the gas supply piping system by closing its individual
manual shutoff valve during any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 psi (3.5 kPa). Use 1/2” diameter pipe (minimum) for up to
25’ of piping. Use 1/2” diameter for longer runs.
IMPORTANT:
When connecting or replacing any gas pipe or fittings, all joints must be sealed with
leak-proof sealing compound approved for use with natural and propane gases. After making
connections, check all joints for leaks using a soapy water solution and brush.
WARNING: Never use an open flame when testing for gas leaks. Use of an open flame could
result in a fire, explosion and bodily harm.
7
4" MINIMUM CLEARANCE
TO ALLOW LID TO
FULLY OPEN