![Turtle Tough TT-MA-DSS Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/turtle-tough/tt-ma-dss/tt-ma-dss_operation-manual_1182460024.webp)
TURTLE
TOUGH
®
24
DO ppm
Measurement
Dissolved Oxygen ppm
Setup Parameter
Configuration
4
N/A
Sensor Type
4
P18
Default Node
4
P02
Default Baudrate
19,200
P03
Default Output Type
4-20mA
P04
Default Polarity
non-inverted
P05
Default Low Whole
0
P06
Default Low Decimal
0
P07
Default Hi Whole
100
P08
Default Hi Decimal
0
P09
Days to Recalibrate
30
P17
DO Units for Output
ppm
P10
Integer Limits
Engineered DO ppm Limits
0
0.00
15,000
150.00
% of Full Range
Engineered DO ppm Units
RTU Integer
0.00%
0.00
0
6.67%
10.00
1000
13.33%
20.00
2000
20.00%
30.00
3000
26.67%
40.00
4000
33.33%
50.00
5000
40.00%
60.00
6000
46.67%
70.00
7000
53.33%
80.00
8000
60.00%
90.00
9000
66.67%
100.00
10000
73.33%
110.00
11000
80.00%
120.00
12000
86.67%
130.00
13000
93.33%
140.00
14000
100.00%
150.00
15000
0.00%
0.00
Default Low Setpoint P06/P07
100.00%
150.00
Default High Setpoint P08/P09
CHANGING DO ppm VALUES ABOVE GET % SCALING COMPUTED
Note 1:
Low and high analog setpoints should be at least 1,000 MODBUS RTU steps apart.