Note:
•
Before switching off main breaker to begin maintenance, please record the sta-
tus code number on the LCD monitor.
•
After maintenance door opened or NFB of charger turned off the charger is still
hazardous. Only visual inspection can be operated.
•
Maintenance of the FSP 600 shall be conducted only by a qualified technician.
•
After opening the front door of the FSP 600, turn off the main breaker and auxil-
iary breaker before any maintenance work.
•
Replace the ventilation filter every six to twelve months.
•
Please confirm the main power junctions are tightened every month, and rotate
cables testing when the power off. If any main power screw is loose will be re-
sulted in damage on charger or smoke on the connections. Please confirm screw
torque requirement table.
•
Charging cable maintenance: Do not twist, bend the charging cable. The metal
contact should not fade or be rusty.
•
Please provide the EVSE information including serial number, model name, sta-
tus code, failure behavior and timing, and also connect the EVSE to the Internet
before remote diagnostics and upgrading