Extend 3 phase 5 wires AC input cables from conduit of concrete base, AC
cables expose at least 400mm (15.75”) and these 5 wires should be with ring
terminals (L1, L2, L3 & N: Inner Diameter: 10.5mm (0.41”), Outer Diameter:
22mm (0.87”) & PE: Inner Diameter: 6.4mm (0.25”), Outer Diameter: 22mm
(0.87”)).
•
The conductor cross sectional area of input power wires should be not less
than 53.5mm² (106 kcmil). If internet is connected via Ethernet, at least
1800mm (71”) of the Ethernet cable must be exposed from the conduit.
STEP 2�
AC Cable
at least 400mm
(15.75 inches)
Ethernet cable 1800mm (71 inches)
(For AC cable conduit)
(For Ethernet cable and
Tilt sensor conduit)
(L Bracket orifice)
screw stick
(Front Direction)
*Unit: mm(inch)
Tilt sensor 400mm(15.7 inches)