Operation
Reading error codes
218
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.16
Reading error codes
The error codes are part of the process input data.
Error code (hex.)
Error code (dec.)
Meaning
0x8000
32768
Channel not active
0x8001
32769
Read/write head not connected
0x8002
32770
Memory full
0x8003
32771
Block size of the tag not supported
0x8004
32772
Length exceeds the size of the read fragment
0x8005
32773
Length larger than the size of the write fragment
0x8006
37774
Read/write head does not support HF bus mode
0x8007
32775
Only one read/write head should be connected for addressing.
0x8100
33024
Parameter undefined
0x8101
33025
Operating mode
parameter outside of the permissible range
0x8102
33026
Tag type
parameter outside of the permissible range
0x8103
33027
Operating mode
parameter in Continuous mode outside of the
permissible range
0x8104
33028
Length
parameter in Continuous mode outside of the permissible range
0x8105
33029
Size of the write fragment outside of the permissible range
0x8106
33030
Size of the read fragment outside of the permissible range
0x81FD
33021
Bridging time
parameter outside of the permissible range
0x81FE
33022
“Address” parameter in Continuous mode outside of the permissible
range
0x81FF
33023
No read/write head selected
0x8200
33280
Command code unknown
0x8201
33281
Command not supported
0x8202
33282
Command not supported in HF applications
0x8203
33283
Command not supported in UHF applications
0x8204
33284
Command for multitag application with automatic tag detection not
supported
0x8205
33285
Command for applications with automatic tag detection not supported
0x8206
33286
Command only supported for applications with automatic tag detection
0x8207
33287
Command not supported for multitag application
0x8208
33288
Command not supported in HF bus mode
0x8209
33289
“Length” parameter outside of the permissible range
0x820A
33290
Address outside of the permissible range
0x820B
33291
Length and address outside of the permissible range
0x820C
33292
No tag found
0x820D
33293
Timeout
0x820E
33294
Next command not supported in multitag mode
0x820F
33295
Length of the UID outside of the permissible range
0x8210
33296
Length outside of the tag specification
0x8211
33297
Address outside of the tag specification
Содержание TBEN-L4-4RFID-8DXP
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN L 4RFID 8DXP RFID Interface...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 59: ...V02 00 2020 08 59 The device appears in the project tree Fig 53 TBEN L 4RFID 8DXP in the project tree...
Страница 242: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100004010 2020 08 100004010...