Operation
Software diagnostic messages
214
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
9.14.3
Diagnostic messages – digital channels
Byte no.
Bit
7
6
5
4
3
2
1
0
0
VAUXC7
VAUXC6
VAUXC5
VAUXC4
Reserved
1
Reserved
2
Reserved
3
ERR15
ERR14
ERR13
ERR12
ERR11
ERR10
ERR9
ERR8
Meaning of the diagnostic bits
Designation
Meaning
VAUXC4
Overcurrent at power supply terminal VAUX at socket 4
(channels 8 and 9)
VAUXC5
Overcurrent at power supply terminal VAUX at socket 5
(channels 10 and 11)
VAUXC6
Overcurrent at power supply terminal VAUX at socket 6
(channels 12 and 13)
VAUXC7
Overcurrent at power supply terminal VAUX at socket 7
(channels 14 and 15)
ERRx
Error message on channel x
9.14.4
Diagnostic messages – module status
Meaning of the diagnostic bits
Designation
Meaning
V2
Undervoltage at power supply connection V2
ARGEE
ARGEE project active
DIAG
Module diagnostics present
FCE
Force mode in the DTM active
COM
Internal error
V1
Undervoltage at power supply connection V1
Byte no.
Bit
7
6
5
4
3
2
1
0
0
V2
ARGEE
DIAG
1
FCE
COM
V1
Содержание TBEN-L4-4RFID-8DXP
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN L 4RFID 8DXP RFID Interface...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 59: ...V02 00 2020 08 59 The device appears in the project tree Fig 53 TBEN L 4RFID 8DXP in the project tree...
Страница 242: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100004010 2020 08 100004010...