Configuring and Parameterizing
Parameters
94
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Parameter name
Value
Description
Swap A/B line
No
yes
The polarity of the A and B lines of the serial in-
terface is reversed (only applies to the RS485
operating mode).
Operation mode
RS232
The interface is operated as RS232 interface.
RS485
The interface is operated as RS485 interface.
Parity
none
No parity
odd
Odd parity (1 bit error detection)
even
Even (1 bit error detection)
8.1.5
Interface parameters – CAN
The parameter can only be set in CODESYS.
Parameter name
Value
Description
Baudrate (kBit/s)
10
20
50
100
125
500
800
1000
Defines the baudrate for the connected CAN
network.