Connecting
USB host port
24
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
6.5
Connecting digital sensors and actuators
The device has four 5-pin M12 connectors for connecting digital sensors and actuators. The
maximum tightening torque is 0.8 Nm.
Fig. 23: M12 connector for connecting digital sensors and actuators
Connect the sensors and actuators to the device according to the figure shown below.
5 FE
4 BK
1 BN +
3 BU –
3 BU –
2 WH
v
C2…C3
Sensor
or
Actuator
Sensor
or
Actuator
Fig. 24: Connectors for digital sensors and actuators - wiring diagram
6.6
Using the USB device port
The USB device port is designed as a mini USB B socket and can be used as a service interface
for the device DTMs and as a programming interface for CODESYS.
1 2 3 4 5
v
1 = 5 VDC
2 = D –
3 = D +
4 = n.c.
5 = GND
Fig. 25: USB device port
RNDIS driver
The RNDIS driver for the USB device port is installed automatically during the DTM installation
in PACTware™. After the DET installation, the USB device port is shown as additional Ethernet
port in the DTM.
NOTE
Use the interface BL Service Ethernet in the DTM for the connection to the device.
6.7
USB host port
The USB host port is designed as a CODESYS 2.0-A socket and is used to connect USB memory
sticks for program backup, program recovery, firmware update and data synchronization.
1 = 5 VDC
2 = D –
3 = D +
4 = GND
1 2 3 4
v
Fig. 26: USB host port
Содержание TBEN-L Series
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN L PLC Compact CODESYS V3 PLC...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 53: ...V02 00 2019 11 53 Fig 57 Configuration of in and output data in TIA Portal CODESYS...
Страница 73: ...V02 00 2019 11 73 Fig 77 Monitoring the task configuration In the example the average cycle time is 47 s...
Страница 105: ...V02 00 2019 11 105 Fig 101 Webserver I O channel diagnostics...
Страница 107: ...V02 00 2019 11 107 Fig 103 Webserver module status...
Страница 126: ...Over 30 subsidiaries and over 60 representations worldwide www turck com D301431 2019 11 D301431...