V02.00 | 2019/11
93
8.1.2
Parameters of the local DXP channels (Local I/O)
Default values are shown in
bold
.
Parameter name
Value
Description
Activate output
No
The output is deactivated.
yes
The output is activated.
Manual output reset after
overcurrent
No
The output switches on automatically after an
overload.
yes
The output is manually switched-off and on
again.
8.1.3
Parameter VAUX Control
Parameter VAUX Control (for sensor/actuator supply)
Default values are shown in
bold
.
Parameter name
Value
Description
VAUX2 Pin 1 Cx (Chy - z)
24 VDC
The 24 VDC sensor/actuator supply at Pin1 of
the connector is switched on.
switchable
The 24 VDC sensor/actuator supply at pin1 of
the respective connector is switchable via the
process data.
off
The 24 VDC sensor/actuator supply at Pin1 of
the connector is switched off.
8.1.4
Interface parameters – COM0/COM1
The parameters can only be set in CODESYS.
Default values are shown in
bold
.
Parameter name
Value
Description
Data rate
9600 bps
Data rate of the serial interface
19.2 kbps
38.4 kbps
57.6 kbps
115.2 kbps
230.4 kbps
Data bits
7 bit
Defines the number of data bits per telegram
8 bit
Stopp bits
1 bit
Defines the number of stop bits
2 bit
Termination active
No
No line termination active
yes
Line termination activated (only valid for oper-
ation mode RS485)
Biasing active
No
Deactivates the biasing resistor
yes
Activates the biasing resistor
Voltage supply VAUX1
off
VAUX1 is switched off
V1 (24 VDC)
VAUX1 from V1 (24 VDC) is switched on
Содержание TBEN-L Series
Страница 1: ...Your Global Automation Partner Instructions for Use TBEN L PLC Compact CODESYS V3 PLC...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Страница 53: ...V02 00 2019 11 53 Fig 57 Configuration of in and output data in TIA Portal CODESYS...
Страница 73: ...V02 00 2019 11 73 Fig 77 Monitoring the task configuration In the example the average cycle time is 47 s...
Страница 105: ...V02 00 2019 11 105 Fig 101 Webserver I O channel diagnostics...
Страница 107: ...V02 00 2019 11 107 Fig 103 Webserver module status...
Страница 126: ...Over 30 subsidiaries and over 60 representations worldwide www turck com D301431 2019 11 D301431...