Setting
Reset to factory settings
➤
➤
Starting the reset to factory settings: Bridge pin 3 (BU) with pin 5 (GY) for 14...19 s.
➤
➤
Confirming the reset to factory settings: Bridge pin 3 (BU) with pin 5 (GY) for 2...7 s.
➤
➥
The device has been successfully reset to the factory settings if the green LED flashes for 1.5 s
at a frequency of 5 Hz.
Set output 2 as a current output
NOTE
If output 2 is set as a current output, the closer teach point corresponds to the 1st limit
value (4 mA) and the teach point further away to the 2nd limit value (20 mA).
➤
➤
Bridge pin 1 (BU) with pin 5 (GY) for 2...7 s.
➤
➤
Set limit values for the window function.
➤
➥
Output 2 is set successfully as a current output if the green LED flashes for 1.5 s at a frequency
of 5 Hz.
Set output 2 as a voltage output
NOTE
If output 2 is set as a voltage output, the closer teach point corresponds to the 1st limit
value (0 V) and the teach point further away to the 2nd limit value (10 V).
➤
➤
Bridge pin 1 (BU) with pin 5 (GY) for 8...13 s.
➤
➤
Set limit values for the window function.
➤
➥
Output 2 is set successfully as a voltage output if the green LED flashes for 1.5 s at a frequency
of 5 Hz.
Set output 2 as a switching output
➤
➤
Bridge pin 1 (BU) with pin 5 (GY) for 14...19 s.
➤
➥
Output 2 is set successfully as a switching output if the green LED flashes for 1.5 s at a fre-
quency of 5 Hz.