Technical data
DC output
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 35
13.2
DC output
Technical data
Number of outputs
4
Output voltage
n
Nominal
24 VDC
Default-setting: 24.5
n
Adjustment range
24… 28 V
Settable in steps: 24 V, 24,5 V,
25 V, 25.5 V, 26 V, 26.5 V, 27 V
and 28 V
Factory setting
Typ. 24.5 V, ± 0,2 %, at nominal load
Line regulation
Max. 10 mV
Linear voltage regulation
Load regulation
Typ. 100 mV
0…600 W output load,
static value
Ripple and noise voltage
Max. 100 mVpp
Bandwidth 20 Hz…20 Mhz,
50 Ω
Output current
Max. 12 A per output,
s. fig.: Trip curve diagram (max. 12A)
Total output power, continu-
ous at ambient temperature
n
At 45 °C
n
At 55 °C
n
At 70 °C
600 W
500 W
350 W
Linear derating b45 °C and +70 °C, s. fig.: Derating output power vs. ambient temper-
ature
Total output power, short-
term, up to 5 s, at ambient
temperature:
n
Up to 55 °C
n
Up to 70 °C
1000 W
700 W
Overload behavior
S. fig.: Trip curve diagram (max. 12 A)
Internal output capacitance
Typ. 12500 μF
For all four outputs in total
Parallel use
No
Do not connect outputs or
devices in parallel.
Back-feeding loads
Max. 35 V/4 J
For all four outputs together,
even when switched off
Trip Delay
/s
I
Out
/A
(typ.)
0
0.1
1
10
0
5
10
15
20
25
2 3 4 5 6
8
10
12 [A]
Fig. 17: Trip curve diagram (max. 12 A)