Setting
Setting the device via IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 23
eFuse pre-alarm level ch… — index 0x6D (109)
This parameter defines the value (in percent) from which a pre-alarm is generated for the sub-
sequent triggering of the eFuse at the respective channel.
Format
Length
32-bit record (UINT8)
8 bit per channel
Sub index
Object name
Bit offset
1
eFuses pre-alarm level Ch1
24
2
eFuses pre-alarm level Ch2
16
3
eFuses pre-alarm level Ch3
8
4
eFuses pre-alarm level Ch4
0
Default values are shown in
bold
.
Unit:
2
-7
%/bit
Value range:
13…192 = 10.17…150 %
Default value:
103 = 80.46875 %
Assignment
Byte
0
1
2
3
Bit offset
31…24
23…16
15…8
7…0
Sub index
1
2
3
4
Bit order
7…0
7…0
7…0
7…0
Trip value
Channel 1
Channel 2
Channel 3
Channel 4