Setting
Setting the device via IO-Link
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | [email protected] | www.turck.com
V01.00 | 2022/09 | 20
8.2.5
Parameters
Parameter overview
Index
Hex.
(dec.)
Sub
index
Parameter name
Data
type
Length
in bit
Unit
Access
Read [R]
Write [W]
0x65
(101)
0
Standby
BOOL
8
RW
0x67
(103)
0
Configuration setting
UINT8
8
RW
0x68
(104)
0
PSU total output current Pre-alarm level
UINT16
16
2
-8
A/bit RW
0x69
(105)
0
Output Voltage Setpoint
UINT16
16
2
-8
V/Bit
RW
0x6A
(106)
0
eFuses channel on/off
Set of
BOOL
8
-
RW
0x6C
(108)
0
eFuse trip value Ch1
UINT16
16
2
-8
A/bit RW
1
…
2
3
eFuse trip value CH4
0x6D
(109)
0
eFuses pre-alarm level Ch1
UINT8
8
2
-7
/Bit
(0.78 %/
Bit)
RW
1
…
2
3
eFuses pre-alarm level Ch4
Standby — index 0x65 (101)
This parameter can be used to actively set the device to the ”standby” state.
Format
Length
BOOL
1 bit
Default values are shown in
bold
.
Value
Meaning
0
False
PSU normal operation
1
True
PSU standby
Power supply in standby mode, all outputs are switched off