Event code Event
Event-type
Description
0x1850
eFuse output current
pre-alarm ch1
Notification
The output current of the eFuse at the channel has
exceeded the pre-alarm level for more than 2 s.
0x1851
eFuse output current
pre-alarm ch2
Notification
0x1852
eFuse output current
pre-alarm ch3
Notification
0x1853
eFuse output current
pre-alarm ch4
Notification
0x4210
Permissible device
temperature exceeded
Warning
The temperature in the device is too high.
0x6320
Parameter error
Error
The parameter settings of the device are invalid.
9.5
IO-Link error codes
Error code
Description
0x8000
No details
Application error in device
Service was denied by device, no detailed information avail-
able
0x8011
Index not available
0x8012
Sub index not available
0x8020
Service temporarily not available
No access to parameters possible, device does not allow ac-
cess in current state
0x8021
Service temporarily not available,
local control
No access to parameters possible, device in local operating
mode, operation only via operator interface on device
0x2022
Service temporarily not available,
device control
No access to parameters possible, device in remote operat-
ing mode, operation only via IO-Link
0x8023
Access denied
Access denied, index not writable
0x8030
Parameter value out of range
0x8031
Parameter value above limit
0x8032
Parameter value below limit
0x8033
Parameter length overrun
Length of data to be written does not match the length
defined for this parameter.
0x8034
Parameter length underrun
0x8035
Function not available
Command not supported by the device
0x8036
Function temporarily unavailable
Command not supported by the device
0x8040
Interfering parameter
Invalid parameter set, a written single parameter value does
not fit to other parameter settings
0x8041
Inconsistent parameter set
Parameters inconsistent, device plausibility check failed
0x8082
Application not ready
Device not ready, access denied