Address Setting for Spanner Modules
5.1
Address setting at TBEN-L…-EN1
Setting the address mode is done through the 3 rotary coding-switches on the gateway.
Mode: Static Rotary
When using the rotary-mode, the last byte of the station’s IP address can be set via the rotary coding
switches.
Switch position
000
: in TURCK devices used to reset the device to the default IP address (see
Resetting the IP-Address, Switch Position "000" (Seite 19)
).
Switch position
001
: normally reserved for the default-gateway
Switch position
002…254
: valid IP address range
Switch position
255
:
normally used for broadcast messages in the subnet.
We therefore recommend addresses in the range of
002…254
.
Mode: BootP (300)
Switch position: 300
Address setting is carried out by a BootP-server in the network after the start-up of the gateway.
PROFINET
Please assure, that in PROFINET applications, the address assigned via a BootP server corre-
sponds to the address, which is assigned in the configuration tool.
Fig. 11: Decimal rotary coding-switches for address setting
ATTENTION!
Protective cover opened
Protection class IP65/IP67/IP69K not guaranteed
Screw the protective cover over the rotary coding-switches firmly
Check if seal of the protective cover is correctly placed
NOTE
After every change of the address-mode, a voltage reset must be done.
NOTE
The IP address, as well as the default subnet mask assigned to the station by the BootP-
server, are stored permanently in the station’s EEPROM.
If the station is switched from BootP-mode to rotary- or PGM-mode, the settings carried
out in BootP-mode (IP address, subnet mask, etc) will be read from the device’s EEPROM.
x 10
x 1
000: 192.168.1.254
1 - 254: static rotary
300: BootP
400: DHCP
500: PGM
600: PGM-DHCP
900: F_Reset
x 100
Содержание 6814035
Страница 1: ...Your Global Automation Partner TBEN L EN1 FEN20 EN1 Spanner Modules Getting Started Guide ...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com ...
Страница 31: ...29 2018 03 6 3 3 EtherNet IP Status and Input Data Mapping Fig 21 Web server EtherNet IP data mapping ...
Страница 32: ...The Web Server Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 30 ...
Страница 55: ...53 2018 03 The spanner can now be used as in the sample above Fig 57 RSLogix FEN20 EN1 in the project ...
Страница 76: ...Appendix Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 74 ...
Страница 77: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100002231 2018 03 100002231 ...