Connecting
4.1
Connecting TBEN-L…-EN1
Connecting the Device to Ethernet
For the connection to Ethernet, the device has an integrated autocrossing switch with two 4-pin
M12 Ethernet sockets. The maximum tightening torque is 0.6 Nm.
Connect the device to the field bus according to the pin assignment shown below.
Connecting the Power Supply
For the connection to the power supply and the feeding through of the power, the device has two
5-pin 7/8" connectors. The power supply connectors are designed as 4-pole (TBEN-L4) or 5-pole
(TBEN-L5) 7/8" connectors. V1 and V2 are galvanically isolated. The maximum tightening torque is
0.8 Nm.
Connect the device to the power supply according to the pin assignment shown below.
Fig. 3: M12 Ethernet sockets
Fig. 4: Pin assignment Ethernet connectors
Supply voltage 7/8“, 5-pole
Pin assignment
X1= voltage IN
X2 = voltage OUT for supplying the next node
V1 = supply voltage 1 (incl. supply of electronics)
V2 = supply voltage 2
v
4
1
3
2
P1, P2
1 = TX +
2 = RX +
3 = TX –
4 = RX –
flange = FE
1 BK = V2 (–)
2 BU = V1 (–)
3 GNYE = FE
4 BN = V1 (+)
5 WH = V2 (+)
3
4
5
2
1
w
v
3
4
5
2
1
X1
X2
Содержание 6814035
Страница 1: ...Your Global Automation Partner TBEN L EN1 FEN20 EN1 Spanner Modules Getting Started Guide ...
Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com ...
Страница 31: ...29 2018 03 6 3 3 EtherNet IP Status and Input Data Mapping Fig 21 Web server EtherNet IP data mapping ...
Страница 32: ...The Web Server Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 30 ...
Страница 55: ...53 2018 03 The spanner can now be used as in the sample above Fig 57 RSLogix FEN20 EN1 in the project ...
Страница 76: ...Appendix Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 74 ...
Страница 77: ...Over 30 subsidiaries and over 60 representations worldwide www turck com 100002231 2018 03 100002231 ...