Operating Instructions

Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com

Operating Instructions

6.1 

General

The device must be registered online: 

www.turck.com/SIL 

or with the supplied SIL registra-

tion card. This must be filled in with all required information upon receipt and sent to Turck.

The device must only be carried out, fitted, installed, operated, commissioned and main-

tained by trained and qualified personnel.

The device is not specified for a certain application. Make sure that application-specific as-

pects are considered.

Data from other documents, e.g. data sheets, is not valid for functional safety operation. 

Devices must be used in cabinets in an typical industrial field environment only. The follow-

ing restrictions describe the operation and storage conditions:

Ensure that the environment complies with the following ratings 

Minimum ambient temperature

-25 °C

Maximum ambient temperature

70 °C

Minimum storage temperature

-40 °C

Maximum storage temperature

80 °C

Maximum air humidity

95 %

Minimum air pressure

80 kPa

Maximum air pressure

110 kPa

The average temperature over a long period of time directly on the exterior sidewall of the 

housing must be maximum 40 °C.

 

ū

The temperature on the exterior sidewall of the housing can deviate considerably from the 

temperature in the control cabinet.

 

ū

The temperature on the exterior sidewall of the housing must be observed in a steady state.

 

ū

In case the temperature on the exterior sidewall of the housing is higher, the failure rates 

from from 

„5.3 FMEDA results“ on page 7

 must be adjusted: 

For a higher average temperature of 60 °C on the exterior sidewall of the housing, the failu-

re rates are multiplied by an experience factor of 2.5.

Ensure that sufficient heat dissipation is provided.

Protect the device from radiated heat and severe temperature fluctuations.

Protect the device from dust, dirt, moisture, shock, vibration, chemical stress, increased 

radiation and other environmental influences.

Ensure a degree of protection of at least IP20 according to IEC 60529 at the mounting 

location.

Ensure that the electromagnetic stress does not exceed the requirements of IEC 61326-3.1.

If there is a visible error, e.g. defective housing the device must not be used.

During operation of the device, surface temperatures may occur that could lead to burns if 

touched.

The device must not be repaired. If problems occur with regard to functional safety, Turck 

must be notified immediately and the device must be returned immediately to: 

 

Hans Turck GmbH & Co. KG 

Witzlebenstraße 7 

45472 Mülheim an der Ruhr 

Germany

Содержание 100000703

Страница 1: ...Your Global Automation Partner IMXK12 AO Analog Signal Isolator Safety Manual...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...esults 7 5 4 Examples for using the results 7 5 4 1 Probability of dangerous failure per hour High Demand mode 7 5 4 2 Average probability of dangerous failure on demand Low Demand mode 7 6 Operating...

Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 5: ...the safety manual at www turck com The English version is considered the definitive document Care was taken in the production of the translations of this document If there is any uncertainty in its in...

Страница 6: ...evice is not specified for a certain application Make sure that the data provided in this chapter is valid for your target application Special application specific factors may cause the premature wear...

Страница 7: ...f 40 C No effect is a failure mode of a component that plays part in implementing the safety func tion but is neither a safe nor a dangerous failure According to IEC 62061 it would be possible to clas...

Страница 8: ...g must be maximum 40 C The temperature on the exterior sidewall of the housing can deviate considerably from the temperature in the control cabinet The temperature on the exterior sidewall of the hous...

Страница 9: ...es with Terminal cross section rigid 0 2 mm to 2 5 mm or flexible 0 2 mm to 2 5 mm When wiring with stranded wires Fix the wiring ends with ferrules Connection via screw terminals Insert the stripped...

Страница 10: ...30 VDC Minimum Power 4 W The proof test see 9 Proof Tests on page 13 shall be executed in order to check the requested function The device shall be locked against unintended operation modification 6...

Страница 11: ...1 V01 0 2019 09 6 4 After operation Undo the terminal connection on the device Remove the device from its rail fixing as shown in the figure Fig 4 Remove device Ensure the proper disposal of the devic...

Страница 12: ...bH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 7 Connection and Wiring Diagrams The pin number assignment can be found at the front label Load resistance A1 800 8 7 GN Pwr RD...

Страница 13: ...ontrolllers or programmable logic for details see 7 4 4 1 3 of IEC 61508 2 9 Proof Tests Proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests This means...

Страница 14: ...H Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10 Document History Document Version Date Modifications 1 0 2019 09 05 Initial version 11 Certificate The certificate can be foun...

Страница 15: ...15 V01 0 2019 09...

Страница 16: ...www turck com Over 30 subsidiaries and over 60 representations worldwide 100010623 2019 09 100010623...

Отзывы: