turck 100000703 Скачать руководство пользователя страница 7

V01.0 | 2019/09 

5.2 

Assumptions

 

Failure rates are constant for 10 years, wear out mechanisms are not included

 

Propagation of failures is not relevant

 

External power supply failure rates are not included

 

All components that are not part of the safety function and cannot influence the safety func-

tion (feedback immune) are excluded.

5.3 

FMEDA results

The following safety characteristic are the results of the FMEDA.

λ

SD

 

λ

SU

 

λ

DD

 

λ

DU

 

No effect

SFF

DC

0 FIT

0 FIT

316 FIT

31 FIT

526 FIT

91 %

91 %

The stated Safe Failure Fraction (SFF) is for reference only. The complete subsystem will need to 

be evaluated to determine the overall SFF.

The failure rates used in this analysis are the basic failure rates from the Siemens standard 

SN 29500 based on the average ambient temperature of components of 40 °C.

“No effect” is a failure mode of a component that plays part in implementing the safety func-

tion but is neither a safe nor a dangerous failure. According to IEC 62061, it would be possible 

to classify the “No effect” failures as “Safe Undetected” failures. Not doing so represents the 

worst-case.

5.4 

Examples for using the results

The following sections provide information about the probability of failures in high demand 

and low demand mode according to IEC 61508.

5.4.1 

Probability of dangerous failure per hour (High Demand mode)

The PFH values are based on a worst-case diagnostic test rate and a reaction time of 50 ms. The 

ratio of the diagnostic test rate to the demand rate shall equal or exceed 100.

PFH

3,0945 E-08 1/h

5.4.2 

Average probability of dangerous failure on demand (Low Demand mode)

With the FMEDA results and the values specified in the following table the average frequency of 

dangerous failure can be calculated exemplarily:

T1

8760 h

MTTR

24 h

 

PFDavg

1,44 E-04

Содержание 100000703

Страница 1: ...Your Global Automation Partner IMXK12 AO Analog Signal Isolator Safety Manual...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...esults 7 5 4 Examples for using the results 7 5 4 1 Probability of dangerous failure per hour High Demand mode 7 5 4 2 Average probability of dangerous failure on demand Low Demand mode 7 6 Operating...

Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 5: ...the safety manual at www turck com The English version is considered the definitive document Care was taken in the production of the translations of this document If there is any uncertainty in its in...

Страница 6: ...evice is not specified for a certain application Make sure that the data provided in this chapter is valid for your target application Special application specific factors may cause the premature wear...

Страница 7: ...f 40 C No effect is a failure mode of a component that plays part in implementing the safety func tion but is neither a safe nor a dangerous failure According to IEC 62061 it would be possible to clas...

Страница 8: ...g must be maximum 40 C The temperature on the exterior sidewall of the housing can deviate considerably from the temperature in the control cabinet The temperature on the exterior sidewall of the hous...

Страница 9: ...es with Terminal cross section rigid 0 2 mm to 2 5 mm or flexible 0 2 mm to 2 5 mm When wiring with stranded wires Fix the wiring ends with ferrules Connection via screw terminals Insert the stripped...

Страница 10: ...30 VDC Minimum Power 4 W The proof test see 9 Proof Tests on page 13 shall be executed in order to check the requested function The device shall be locked against unintended operation modification 6...

Страница 11: ...1 V01 0 2019 09 6 4 After operation Undo the terminal connection on the device Remove the device from its rail fixing as shown in the figure Fig 4 Remove device Ensure the proper disposal of the devic...

Страница 12: ...bH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 7 Connection and Wiring Diagrams The pin number assignment can be found at the front label Load resistance A1 800 8 7 GN Pwr RD...

Страница 13: ...ontrolllers or programmable logic for details see 7 4 4 1 3 of IEC 61508 2 9 Proof Tests Proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests This means...

Страница 14: ...H Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10 Document History Document Version Date Modifications 1 0 2019 09 05 Initial version 11 Certificate The certificate can be foun...

Страница 15: ...15 V01 0 2019 09...

Страница 16: ...www turck com Over 30 subsidiaries and over 60 representations worldwide 100010623 2019 09 100010623...

Отзывы: