Product Description

The analog signal isolators IMXK12-AO are designed to transfer standard galvanic isolated cur-

rent signals from the safe area into the explosion hazardous area in a 1:1 transmission mode. 

In addition to the analog signals, digital HART communication signals can be transferred 

bidirectional.

Output A1 is assigned to input E1.

Typical applications are the control of I/P converters as well as indicator displays and actuator.

4.1 

Safety function

If a current less than 3.6 mA flows into input [E1], a current less than 3.6 mA flows out of the cor-

responding output [A1] within maximum 50 ms.

The transmission of the 4…20 mA current is not part of the safety function.

The LED state is not part of the safety function.

4.2 

Safe state

In the safe state a current less than 3.6 mA flows out of output [A1].

Safety Planning

This chapter provides information for planning a safety-related loop.

The device is not specified for a certain application. Make sure that the data provided in this 

chapter is valid for your target application.

Special application-specific factors may cause the premature wear of the device and must be 

taken into consideration when planning systems; take special measures to compensate for a 

lack of experience based values, e.g. through implementation of shorter test intervals. 

The suitability for specific applications must be assessed by considering the particular overall 

safety-related system with regard to the requirements of IEC 61508.

Safety-planning must only be carried out by trained and qualified personnel. If there is any 

doubt contact Turck directly.

5.1 

Architectural specifications

Due to architectural considerations the following characteristics are specified:

Type

A

HFT

0

Experience has shown that the useful lifetime often lies within a range of 8 to 12 years. It can 

be significantly less if elements are operated near their specification limits. However, it can 

be extended by appropriate measures. For example, heavy temperature fluctuations could 

potentially decrease the useful lifetime, as constant temperature below 40 °C could potentially 

increase the useful lifetime.

Содержание 100000703

Страница 1: ...Your Global Automation Partner IMXK12 AO Analog Signal Isolator Safety Manual...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...esults 7 5 4 Examples for using the results 7 5 4 1 Probability of dangerous failure per hour High Demand mode 7 5 4 2 Average probability of dangerous failure on demand Low Demand mode 7 6 Operating...

Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 5: ...the safety manual at www turck com The English version is considered the definitive document Care was taken in the production of the translations of this document If there is any uncertainty in its in...

Страница 6: ...evice is not specified for a certain application Make sure that the data provided in this chapter is valid for your target application Special application specific factors may cause the premature wear...

Страница 7: ...f 40 C No effect is a failure mode of a component that plays part in implementing the safety func tion but is neither a safe nor a dangerous failure According to IEC 62061 it would be possible to clas...

Страница 8: ...g must be maximum 40 C The temperature on the exterior sidewall of the housing can deviate considerably from the temperature in the control cabinet The temperature on the exterior sidewall of the hous...

Страница 9: ...es with Terminal cross section rigid 0 2 mm to 2 5 mm or flexible 0 2 mm to 2 5 mm When wiring with stranded wires Fix the wiring ends with ferrules Connection via screw terminals Insert the stripped...

Страница 10: ...30 VDC Minimum Power 4 W The proof test see 9 Proof Tests on page 13 shall be executed in order to check the requested function The device shall be locked against unintended operation modification 6...

Страница 11: ...1 V01 0 2019 09 6 4 After operation Undo the terminal connection on the device Remove the device from its rail fixing as shown in the figure Fig 4 Remove device Ensure the proper disposal of the devic...

Страница 12: ...bH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 7 Connection and Wiring Diagrams The pin number assignment can be found at the front label Load resistance A1 800 8 7 GN Pwr RD...

Страница 13: ...ontrolllers or programmable logic for details see 7 4 4 1 3 of IEC 61508 2 9 Proof Tests Proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests This means...

Страница 14: ...H Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10 Document History Document Version Date Modifications 1 0 2019 09 05 Initial version 11 Certificate The certificate can be foun...

Страница 15: ...15 V01 0 2019 09...

Страница 16: ...www turck com Over 30 subsidiaries and over 60 representations worldwide 100010623 2019 09 100010623...

Отзывы: