Terms and Abbreviations

DC

Diagnostic Coverage

FIT

1 FIT is 1 failure per 10E09 hours

FMEDA

Failure Modes, Effects and Diagnostic Analysis

HFT

Hardware failure tolerance

λ

AU

Undetected Annunciation failure rate (per hour)
Annunciation failures do not directly impact safety but impact the ability to detect a future 
fault (such as a fault in diagnostic circuit).

λ

DD 

Detected dangerous failure rate (per hour)

λ

DU

 

Undetected dangerous failure rate (per hour)

λ

SD

Detected safe failure rate (per hour)

λ

SU

Undetected safe failure rate (per hour)

MTTR

Mean time to restoration (hour)

PFD

avg

Average probability of failure on demand

PFH

Probability of dangerous failure per hour

SFF

Safe Failure Fraction

SIL

Safety Integrity Level

T1

Proof test interval (hour)

Type A

“Non-complex” element (all failure modes are well defined); for details see 7.4.4.1.2 of 
IEC 61508-2

Type B

“Complex” element (using micro controlllers or programmable logic); for details see 7.4.4.1.3 
of IEC 61508-2

Proof Tests

Proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic 

tests. This means that it is necessary to specify how dangerous undetected faults which have 

been noted during the FMEDA can be detected during proof testing.

Ensure that the proof test is only carried out by qualified personnel.

A suggested proof test consists of the following steps:

Step

Action

1.   

Bypass the safety functions and take appropriate action to avoid a false trip.

2.   

Provide appropriate input-/control signals to the interface modules and verify the ex-
pected signal input/output conditions for the interfaces.

3.   

Verify if internal fault detection is working in case it is activated.

4.   

Provide appropriate input-/control signals to the interface modules and verify that the 
safety function is carried out correctly.

5.

Remove the bypass and otherwise restore normal operation.

Once the test has been completed, document and archive the results.

This test will detect 95 % of possible dangerous undetected failures.

Содержание 100000703

Страница 1: ...Your Global Automation Partner IMXK12 AO Analog Signal Isolator Safety Manual...

Страница 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 3: ...esults 7 5 4 Examples for using the results 7 5 4 1 Probability of dangerous failure per hour High Demand mode 7 5 4 2 Average probability of dangerous failure on demand Low Demand mode 7 6 Operating...

Страница 4: ...4 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...

Страница 5: ...the safety manual at www turck com The English version is considered the definitive document Care was taken in the production of the translations of this document If there is any uncertainty in its in...

Страница 6: ...evice is not specified for a certain application Make sure that the data provided in this chapter is valid for your target application Special application specific factors may cause the premature wear...

Страница 7: ...f 40 C No effect is a failure mode of a component that plays part in implementing the safety func tion but is neither a safe nor a dangerous failure According to IEC 62061 it would be possible to clas...

Страница 8: ...g must be maximum 40 C The temperature on the exterior sidewall of the housing can deviate considerably from the temperature in the control cabinet The temperature on the exterior sidewall of the hous...

Страница 9: ...es with Terminal cross section rigid 0 2 mm to 2 5 mm or flexible 0 2 mm to 2 5 mm When wiring with stranded wires Fix the wiring ends with ferrules Connection via screw terminals Insert the stripped...

Страница 10: ...30 VDC Minimum Power 4 W The proof test see 9 Proof Tests on page 13 shall be executed in order to check the requested function The device shall be locked against unintended operation modification 6...

Страница 11: ...1 V01 0 2019 09 6 4 After operation Undo the terminal connection on the device Remove the device from its rail fixing as shown in the figure Fig 4 Remove device Ensure the proper disposal of the devic...

Страница 12: ...bH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 7 Connection and Wiring Diagrams The pin number assignment can be found at the front label Load resistance A1 800 8 7 GN Pwr RD...

Страница 13: ...ontrolllers or programmable logic for details see 7 4 4 1 3 of IEC 61508 2 9 Proof Tests Proof tests shall be undertaken to reveal dangerous faults which are undetected by diagnostic tests This means...

Страница 14: ...H Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 10 Document History Document Version Date Modifications 1 0 2019 09 05 Initial version 11 Certificate The certificate can be foun...

Страница 15: ...15 V01 0 2019 09...

Страница 16: ...www turck com Over 30 subsidiaries and over 60 representations worldwide 100010623 2019 09 100010623...

Отзывы: