Technical Specifications
Power Voltage
115 Vac 50-60 Hz ± 10 %
230 Vac 50-60 Hz ± 10 %
Alternative Power Voltage
Upon Request
24 Vac ± 10 %
24 Vdc ± 10 %
Output Voltage For Solenoid
115 Vac 50-60 Hz ± 10 %
230 Vac 50-60 Hz ± 10 %
24 Vac ± 10 %
24 Vdc ± 10 %
Inputs
from 4 to 20mA x 1
Outputs Proportionate To Dp Value
For Remote Pressure Reading
from 4 to 20mA x 1
Power Consumption
28 Watts Maximum Load
Alarm Relays
3 Normally Closed
Display
Graphic LCD Backlit Monochromatic
B/W 128 x 64 Pixel
Glass Fuse 5 x 20 mm
115 or 230 Vac 1 x 1 A
24 Vac or 24 Vdc 1 x 3 A
Operating Temperature
-10 °C - 55 °C
Storage Temperature
-20 °C - 60 °C
Environmental Humidity
0 ÷ 95% Relative
Non Condensing
Valve Opening Impulse Time
50 m.sec. - 10 s
Interval Pause Time Between
Valve Opening
1 sec. – 7200 sec.
Measurable Pressure
0 - 10 kPa
Maximum Pressure Applicable
To The Gauge
50 kPa – 0.5 bar
Higher pressures will
damage the device
Casing
ABS Base
Polycarbonate Cover
Protection Degree From Water And Dust IP65 DIN EN 60529
Shock Resistance
IK07 2 Joule (EN62262).