24
Mode
Setting
(Set Number)
Optional output
PhotoMOS compare output
This is the setting change method of photoMOS compare output. operate following the setting
code No. mentioned on page 17.
Code No.41
『
AL1 Comparative value
』
Code No.42
『
AL2 Comparative value
』
Code No.43
『
AL3 Comparative value
』
Code No.44
『
AL4 Comparative value
』
Code No.45
『
Batch switching
』
Set the comparative value of AL1,AL2,AL3,AL4
Setting range
:
0 to 999999
AL3 to 4 totalized value alarm output, change
of batch output totalized value alarm output
can switch to upper limit and upper limit alarm
output or totalized value batch output.
Regardless of the display, it compares
sequentially with counter data.
Relay output delay is MAX 20 ms.
・
Comparison condition
Totalized alarm output:
Totalized value
>
Upper limit set value
・・・
AL3 ON
(
AL3 light up
)
Totalized value
>
Upper / upper limit set value
・・・
AL4 ON
(
AL4 light up
)
Batch output
:
In the two-stage setting of AL 3 and AL 4,
when the totalized value becomes equal with
the setting value, output of the relay is
obtained with ON pulse.
Pulse width can be selected arbitrarily by code
No. 46: AL3 output width, code No. 47: AL4
output width.
AL 4 is also equipped with an auto reset ON /
OFF function of totalized value.
Setting range : 0 (Totalized alarm output)
1 (batch output)
Change of comparison output AL1 from
100000 to 20000
ENTER
▲
SET
MODE
MODE
SET
SET
▲
MODE
SET
MODE
ENTER
MODE
To code No,setting
Code
№
41
To measurement
operation
1sec.
current setting
Memory
,
▲
Change of setting
ENTER
1sec.
ENTER
1sec.
1sec.
Displays of