![TSUJI ELECTRONICS CT08-ER2 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/tsuji-electronics/ct08-er2/ct08-er2_user-manual_1178497030.webp)
Type of command
GSDRDX?xxxxyyyy(K)
Read out acquired data from data address of xxxx to yyyy in decimal.
xxxx, yyyy :When you input below 3 digits number, please put 0 on head and 4 digits.
If K is attached to an end, it expresses x1000. Please use this for 9999 or more numbers.
Ex. GSDRD?01234567
This is an example of reading out data address from 123 to 4567.
ch0 ch1 ch2 ・・・・ ch31 timer
Reply example: 02123, 00456, 07890, ・・・・・ , 01234, 234567
← Data of No.123
03123, 00456, 07890, ・・・・・ , 01234, 234567
← Data of No.124
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
04123, 00456, 07890, ・・・・・ , 01234, 234567
← Data of No.4567
Data are output in order counter ch0 to ch31 and timer on one line.
Each data is output at 5 digits added 0 on head if the number of digit is below 5.
If over 5, each data is output at maximum digits of them.
Type of command
GSDRDH?xxxxyyyy
Read out stored data from data address of xxxx to yyyy in hexadecimal.
Type of command
GSDRDXH?xxxxyyyy(K)
Read out stored data of all ch and timer from data address of xxxx to yyyy in hexadecimal.
High-speed reading (more than 1MB/s) is possible at LAN connection.
If K is attached to an end, it expresses x1000. Please use this for 9999 or more numbers.
Type of command
GSCRD?uvwxxxxyyyy
Read out stored data from data address of xxxx to yyyy.
u:read out start channel v:end channel w: if 1,read out timer data, if 0, don' t read.
xxxx, yyyy :When you input below 3 digits number, please put 0 on head and 4 digits.
Ex. GSCRD?24101234567
This is an example of reading out data address from 123 to 4567 of ch2 to 4, and timer.
ch2 ch3 ch4 timer
Reply example: 02123, 00456, 07890, 234567
← Data of No.123
02123, 00456, 07890, 234567
← Data of No.124
・・・・・・・・・・・・・・・・・・・・・・・・・・・・・・
04123, 00456, 07890, 234567
← Data of No.4567
Data are output in order required counter (ch0 to ch7) and timer on one line.
Each data is output at 5 digits added 0 on head if the number of digit is below 5.
If over 5, each data is output at maximum digits of them.
Type of command
GSCRDX?uuvvwwxxxxyyyy(K)
Read out stored data from data address of xxxx to yyyy.
uu:read out start channel vv:end channel ww: if 01,read out timer data, if 00, don' t read.
xxxx, yyyy :When you input below 3 digits number, please put 0 on head and 4 digits.
If K is attached to an end, it expresses x1000. Please use this for 9999 or more numbers.
Ex. GSCRDX?02040101234567
This is an example of reading out data address from 123 to 4567 of ch2 to 4, and timer.
30/43