PROBLEM
CAUSE
WHAT TO DO
WATER FLOW
ERROR
CHECK
WATER FLOW
INSIDE HEAT
PUMP
The water flow
inside the heat
pump is
insufficient;
The bypass
valves are in the
wrong position;
There is no
water circulation
inside the heat
pump;
The flow
switch is
defective.
Make sure the
circulating pump
works;
Make sure the
bypass valves are
properly positioned;
Check the skimmer
(no obstruction).
DEFROST
MODE
The heat pump
is in de-icing
mode. This Is
Normal if outside
temperatures are
low
Wait until the end of
the de-icing cycle.
The heat pump will
restart automatically.
ERROR
LOW
REFRIGERANT
PRESSURE
Ventilation on
the evaporator is
insufficient
The fan does
not work
Refrigerant
leak
The outside
temperature is
too low
Check that the
evaporator is not
obstructed by pollen,
grass, leaves; see the
user’s manual for
safety and
maintenance tips;
Be sure there is
enough free space
around the heat pump
(see the Installation
Guide);
Check that the fan
is powered ON
LOW
PRESSURE
FAILED 3
TIMES
IN 1 HOUR
RESET THE
BREAKER
The heat pump
low switch has
cut off three (3)
times in the
same hour for
one of the
reasons
above.(code LP)
The heat pump will
not re-start after one
of the protection
devices shuts it down
for the third time in
the same hour
Close the circuit
breaker to reset the
heat pump
ERROR
HIGH
REFRIGERANT
PRESSURE
The water flow
inside the heat
pump is
insufficient
The bypass
valves are in the
wrong position
The water exit
is blocked
There is an
obstruction in
the refrigeration
circuit (piping
blocked)
Check whether
there is adequate
water circulation
inside
Check that the
bypass valves are
properly positioned
Check if there is an
object obstructing the
water hose
HIGH
PRESSURE
FAILED 3
TIMES
IN 1 HOUR
RESET THE
BREAKER
The heat pump
high pressure
switch has cut
off three (3)
times in the
same hour for
one of the
reasons above
(code HP)
The heat pump will
not re-start after one
of protection devices
shuts it down for the
third time in the same
hour
Close the circuit
breaker to reset the
heat pump
PROBLEM
CAUSE
Digital control
displays
CODE : FLO
The water flow inside the heat pump is insufficient
There is no water circulation inside the heat pump
The flow switch is defective
CODE : FS
The heat pump is in de-icing mode
CODE : LP
Ventilation on the evaporator is insufficient
The fan does not work
Refrigerant leak
The outside temperature is too low
CODE : LP3
The heat pump flow switch has cut off three (3)
times in the same hour for one of the reasons above
(code LP)
CODE : HP
The water flow inside the heat pump is insufficient
The bypass valves are in the wrong position
The water exit is blocked
There is an obstruction in the refrigeration circuit
(piping blocked)
CODE : HP3
The heat pump high pressure switch has cut off three
(3)
times in the same hour for one of the reasons above
(code HP)
CODE : SPI
The digital control is defective
CODE : DPO
The de-icing sensor is not properly connected or is not
receiving power
CODE : PO
The water temperature sensor is not properly
connected or is
not receiving power
CODE : DPC
The de-icing sensor is defective
CODE : PC
The water temperature sensor is defective
Is needed, the
fan is
functioning, no
code is
displayed and
the
compressor
does not start
Electrical problem in the compressor circuit
Capacitor defective
compressor defective