5-5.Set the module’s configuration
*The module must be reboot, When you set up module’s configuration after.
Command
%IDNNTTBBDD(CHK)(cr)
Syntax
Description
%
First leading code
ID
Address of setting module from 00~FF(HEX)
NN
New address of setting from 00~FF(HEX)
TT
Analog input type setting
BB
New baud rate setting
DD
Data Format
CHK
Checksum
(cr)
Carriage return
Response
!ID(CHK)(cr)
Command valid
?ID(CHK)(cr)
Command Invalid
5-6. (TT) Analog input type
5-7. (BB) Baud Rate Setting
Type Code
08
09
0A
0B
0C
0D
Voltage:
±
10V
±5
V
±
2.5V
±
1.25V
±
650mV
±
20mA
% of FSR
±100 %
±100 %
±100 %
±100 %
±100 %
±100 %
2’S
complem
ent
Fast
Mode
0000~8000~FFFF 0000~8000~FFFF
0000~8000~FFFF
0000~8000~FFFF
0000~8000~FFFF
0000~8000~FFFF
Normal
Mode
000000~800000~
FFFFFF
000000~800000~F
FFFFF
000000~800000~F
FFFFF
000000~800000~F
FFFFF
000000~800000~F
FFFFF
000000~800000~F
FFFFF