Full calibration (100% or 20mA Calibration)

Switches 1, 2, 3 & 4 must be 
OFF (#5 is as per range).
Fill the material up to the 
desired level

Turn ON Switch# 2

Make sure that
switch 1, 3 & 4 are 
OFF (as shown above).
And switch 5 is as per 
range

LED will blink faster (not as faster
as Error blink) for 5sec. During this 
time the switch can be put back if 
accidently turned ON. Then LED 
will start blinking three times then 
off, successively. mA meter will 
show 4mA

Wait till mA meter shows 20mA.
And status LED glows permanently.
Turn-off switch# 2, 20mA level 
or 100% level is calibrated.

4 mA
20 mA
trim (de cre as e )
trim (incre as e )

to set

turn-on

T

rimming

4 mA
20 mA
trim (de cre as e )
trim (incre as e )

to set

turn-on

T

rimming

Trimming can be done. If 20mA reading in
mili-ammeter is lesser or more than 20mA. 
Use the trim-switches 
(switch# 3 to decrease, say 20.3 mA to 20.0)
(switch# 4 to increase, say 19.7 mA to 20.0).

Trimming (100% or 20mA)

Empty calibration (0% or 4mA Calibration) 

Switches1, 2, 3 & 4 must be 
OFF (#5 is as per range). 
Empty the material to the 
desired level. 

Turn ON Switch# 1

Make sure that switch 
2, 3 & 4 are OFF
(as shown above).
And switch 5 is as per 
range

LED will blink faster (not as faster 
as Error blink) for 5sec. During this 
time the switch can be put back if
accidently turned ON. Then LED 
will start blinking three times then 
off, successively. mA meter will 
show 20mA

Wait till mA meter shows 4mA. 
And status LED glows permanently.
Turn-off switch# 1, 4mA level 
or 0% level is calibrated.

Calibrate 4mA

 for

 0% Level

Trimming (0% or 4mA)

4 mA
20 mA
trim (de cre as e )
trim (incre as e )

to set

turn-on

T

rimming

4 mA
20 mA
trim (de cre as e )
trim (incre as e )

to set

turn-on

T

rimming

Trimming can be done. If 4mA reading 
in mili-ammeter is lesser or more than 4mA 
Use the trim-switches
(switch# 3 to decrease, say 4.1 mA to 4.0)
(switch# 4 to increase, say 3.7 mA to 4.0)

status

For trimming 100% (20mA)
a) Turn switch 3/4 (decrease/increase) ON
b) Turn 20mA switch ON
(this sequence is important). 
and watch the mili-ammeter till correct
trimming of 20mA is done. Immediately
a) Turn switch 3/4 (decrease/increase) OFF
b) Turn 20mA switch OFF (sequentially).

For trimming 0% (4mA)
a) Turn switch 3/4 (decrease/increase) ON
b) Turn 4mA switch ON
(this sequence is important). 
and watch the mili-ammeter till correct
trimming of 4mA is done. Immediately
a) Turn switch 3/4 (decrease/increase) OFF
b) Turn 4mA switch OFF (sequentially).

1. Turn switch 3 ON (switch no. 1, 2 & 4 should be off) 
2. LED will blink rapidly, then it will turn OFF.
3. Once LED is OFF, turn switch 1 ON, LED will turn ON.
4. Turn switch 1 OFF, LED will turn OFF. damping is set to 1 sec.
5. Repeat operation 3 and 4 for as many seconds of damping required, to finish setting, turn all switches OFF.

Damping(response time)

Calibrate 20mA

 for

 100% Level

1 2

3 4

5

1 2

3 4

5

1 2 3 4 5 6 7 8 9

decrease/damping

20mA/5V/10V

increase

U

12 to 60 VDC

!

status

(100%)

4mA/1V/2V

(0%)

to set

turn-on

TLC2

4..20mA o/p

1500pF

4200pF

Range

1..5V 2..10V*

*Min Supply U > 21.5V

Vo

1 2

3 4

5

1 2

3 4

5

1 2 3 4 5 6 7 8 9

decrease/damping

20mA/5V/10V

increase/Water

U

12 to 60 VDC

!

status

(100%)

4mA/1V/2V

(0%)

to set

turn-on

TLC2

4..20mA o/p

1500pF

4200pF

Range

1..5V 2..10V*

*Min Supply U > 21.5V

Vo

1 2 3 4 5 6 7 8 9

decrease/damping

20mA/5V/10V

increase/Water

U

12 to 60 VDC

!

status

(100%)

4mA/1V/2V

(0%)

to set

turn-on

TLC2

4..20mA o/p

1500pF

4200pF

Range

1..5V 2..10V*

*Min Supply U > 21.5V

Vo

1 2

3 4

5

status

LED must be 
blinking once per 
2 sec (No Error).
MiliAmmeter must 
be connected in 
series with the device

status

LED must be 
blinking once per 
2 sec (No Error).
MiliAmmeter must 
be connected in 
series with the device

1 2 3 4 5 6 7 8 9

decrease/damping

20mA/5V/10V

increase

U

12 to 60 VDC

!

status

(100%)

4mA/1V/2V

(0%)

to set

turn-on

TLC2

4..20mA o/p

1500pF

4200pF

Range

1..5V 2..10V*

*Min Supply U > 21.5V

Vo

1 2

3 4

5

1 2 3 4 5 6 7 8 9

decrease/damping

20mA/5V/10V

increase

U

12 to 60 VDC

!

status

(100%)

4mA/1V/2V

(0%)

to set

turn-on

TLC2

4..20mA o/p

1500pF

4200pF

Range

1..5V 2..10V*

*Min Supply U > 21.5V

Vo

1 2 3 4 5 6 7 8 9

decrease/damping

20mA/5V/10V

increase

U

12 to 60 VDC

!

status

(100%)

4mA/1V/2V

(0%)

to set

turn-on

TLC2

4..20mA o/p

1500pF

4200pF

Range

1..5V 2..10V*

*Min Supply U > 21.5V

Vo

status

1 2

3 4

5

1 2

3 4

5

Turn switch 3 ON

Turn switch 1 ON

1 2

3 4

5

Annexure-1

tlc2-manual-annexure-1

www.trumen.in

Page 3

Calibration

 - 

TLC2 (EILV/ERLV)

Decrease

Increase

Decrease

Increase

1 2

3 4

5

1 2

3 4

5

1 2

3 4

5

Turn switch 1 OFF

Turn all switches OFF

Operation 1, 2

Operation 3

Operation 4

Operation 5

Damping=1 sec

status

status

Содержание TLC2

Страница 1: ...ual sensing matters 39 Mangal Nagar Behind Sai Ram Plaza Near Rajiv Gandhi Circle AB Road Indore MP 452 001 India Phone 91 731 497 2065 Trumen Technologies Pvt Ltd Customer Support Phone 91 731 656 24...

Страница 2: ...Operation Matrix TLC SS EIR Page1 Annexure 2 Page1 Page2 Page3 sensing matters Calibration TLC2 EILV ERLV Connection Diagrams TLC2 EILV ERLV Page2 Page3 1 Grounding Load Page2 2 Floating Load Page2 3...

Страница 3: ...ormed with the aid of on site calibration also called wet calibration The probe forms a capacitance with the metalic tank wall The capacitance is sum of three capacitance 4 20 mili Ampere L low Level...

Страница 4: ...y outputs and re transmission over galvanically isolated 4 20mA output SA 80 260VAC 50 60Hz for AC version SD 16 to 32VDC for DC version SPDT 5 A each 24VDC or 220VAC 3 SPDT relays in IP65 max 6 SPDT...

Страница 5: ...uminium housing 5 Make sure process connection is same as that in hopper tank 6 Transmitter probe should never be 6 1 Bent 6 2 Held from thin part 6 3 Cut or machined in any way 6 4 Extended by weldin...

Страница 6: ...way female connector from sensor probe Cable glands Thermal spacer where needed Process connection Stilling well tube Device enclosure Shown on the left are various parts of TLC2 capacitance level sw...

Страница 7: ...d 4 increase 3 Digital Trim decrease Switch 4 Digital Trim increase Switch Switch 4 also act as diagnostic switch 5 Range Switch select for 1500pF to 4200pF 1500pF is required for oil and water up to...

Страница 8: ...SCADA 1 2 3 4 5 6 7 8 9 decrease damping 100 20mA 5V 10V increase U 12 to 60 VDC status to set turn on TLC2 4 20mA o p 1500pF 4200pF Range 1 5V 2 10V Min Supply U 21 5V Vo 0 4mA 1V 2V 3 Voltage Output...

Страница 9: ...witch 3 4 decrease increase ON b Turn 4mA switch ON this sequence is important and watch the mili ammeter till correct trimming of 4mA is done Immediately a Turn switch 3 4 decrease increase OFF b Tur...

Страница 10: ...ill show 20mA Voltmeter will show 5 0V 10 0V LED Indication 4mA or 0 Level 4 mA 20 mA trim decrease trim increase ON 1 2 3 4 When the material in tank is at 0 All switches are OFF LED will blink once...

Страница 11: ...Probe is too long Error is indicated by 21 0mA in loop decrease damping 100 20mA 5V 10V increase 0 4mA 1V 2V 1500pF 4200pF Range 1 2 3 4 5 Status LED Indications TLC2 EILV ERLV Annexure 1 tlc2 manual...

Страница 12: ...ical Connections TLC2 EILV ERLV Annexure 1 tlc2 manual annexure 1 www trumen in Page 6 DC Supply min 12V max 60V Not used TLC2 increase Not used DC Supply min 12V max 60V Voltage output on terminals 2...

Отзывы: