This model is best suitable for continuous current level measurement, as well as continuous
voltage measurement with option 1 to 5V and 2 to 10 VDC.
www.trumen.in
Operation Matrix
-
TLC2 (EILV / ERLV)
Annexure-1
tlc2-manual-annexure-1
Page 4
Calibration
Switches
Material &
Installation
Switching
Operation
When the material
in tank is at 100%.
All switches are
OFF. LED will
blink once per
2sec and mA
meter will show
20mA/ Voltmeter
will show 5.0V/
10.0V
LED
Indication
4mA
or
0% Level
4 mA
20 mA
trim (decrease)
trim (increase)
ON
1 2 3 4
When the material
in tank is at 0%.
All switches are
OFF. LED will
blink once per
2sec mA meter
will show 4mA /
Voltmeter will
show 1.0V/2.0V
20mA
or
100% Level
4 mA
20 mA
trim (decrease)
trim (increase)
ON
1 2 3 4
LED will
blink once
per 2sec
Current
meter
shows
20mA.
Current
Output
Voltage
Output
1-5V
Option
Voltage
Output
2-10V
Option
Volt meter
shows
5.0V
Volt meter
shows
10.0V
LED will
blink once
per 2sec
Current
meter
shows
4.0mA.
Volt meter
shows
1.0V.
Volt meter
shows
2.0V.