Technical data
Designation
Value
Primary air volume flow rate
8 – 57 l/s, 29 – 205 m³/h
Cooling capacity
Up to 1600 W
Heating capacity
Up to 1000 W
Max. operating pressure, water side
10 bar (in combination with connection hoses 6 bar)
Max. operating temperature
75 °C
(55 °C when using flexible connecting hoses)
Minimum operating temperature
6 °C
NOTICE!
Water damage by condensate!
An undershooting of the dew point temperature causes water damage to the device or building due to
condensate.
The chilled water flow temperature must be adjusted so that an undershooting of the dew point is
excluded.
Technical data
Active chilled beams Type DID-E2
4