background image

10

EN

local air conditioner PAC 3500 X

No. Designation

Meaning

27

Fan speed

 LEDs

Fan speed indication:

Stage 1 = low
Stage 2 = high
Stage 3 = maximum

28 Segment display Display of current room temperature

Indication of the target temperature
Indication of the number of hours
during timer programming
Indication of the error code, see
chapter Errors and faults

29 Remote control

transmitter/
receiver

For infrared transmission to the device

30 Display

Indication of different device functions

Info

An acoustic signal is emitted each time a setting is
activated.

Switching the device on

1. Allow the device to rest for a time.
2. Once you have completely installed the device as

described in the Start-up chapter, you can switch it on.

3. Press the 

ON/OFF

 button (16).

ð

The device will be switched on in 

automatic operation

.

4. Select the desired operating mode.

The device automatically deactivates the operating modes
cooling and dehumidification when the condensation tray is full.
The 

water filling level

 LED (15) lights up and an acoustic signal

is emitted.

Setting the operating mode

The device has the following operating modes:

automatic operation

cooling

dehumidification

ventilation

Automatic operation

In 

automatic operation

 mode the 

cooling

 or 

ventilation

 process

will be regulated depending on the ambient temperature and the
preset target temperature of 24 °C.

1. Press the 

MODE

 button (18) until the LED for 

automatic

operation

 (19) is illuminated.

ð

If the ambient is > 25 °C, the device will automatically
operate in cooling mode. The LEDs for 

automatic

operation

 (19), 

cooling

 (19), 

fan speed

 (27) and possibly

compressor operation

 (17) are illuminated. When

combining automatic operation and ventilation, the
desired fan speed may be set using the 

SPEED

button (26).

ð

At an ambient temperature of ≤ 25 °C the device
automatically switches over to fan operation. The LEDs
for 

automatic operation

 (19), 

ventilation

 (19) and 

fan

speed

 (27) are illuminated. When combining automatic

operation and ventilation, the desired fan speed may be
set using the 

SPEED

 button (26).

Cooling

In 

cooling

 mode the room will be cooled down to the desired

target temperature.

1. Press the 

MODE

 button (18) until the 

cooling

 LED (19) is

illuminated.

ð

Cooling

 mode is selected.

ð

The target temperature is indicated on the segment
display (28).

2. Select the desired target temperature by use of the

Decrease value

 (22) or 

Increase value

 (23) button.

Temperatures between 18 °C and 32 °C can be selected.

ð

The desired target temperature flashes on the segment
display (28) for approx. 5 s.

ð

The compressor possibly switches on and the LED for

compressor operation

 (17) is illuminated.

Dehumidification

In 

dehumidification

 mode the humidity level in the room is

reduced.
The temperature cannot be adjusted and the fan runs at the
lowest speed level.

Info

Remove the exhaust air hose during 

dehumidification

,

otherwise the performance will be insufficient.

1. Press the 

MODE

 button (18) until the 

dehumidification

LED (19) is illuminated.

ð

Dehumidification

 mode is selected.

ð

The current room temperature is indicated on the
segment display (28).

ð

The temperature and the fan speed (stage 1) are preset
in this operating mode and cannot be changed.

Info

If the device is operated in a very humid environment,
the accumulating condensate must be discharged at
regular intervals (see chapter Condensate discharge).

Содержание PAC 3500 X

Страница 1: ...TRT BA PAC3500X TC2014 08 008 EN PAC 3500 X EN OPERATING MANUAL LOCAL AIR CONDITIONER ...

Страница 2: ...anual carefully before starting or using the device Always store the manual in the immediate vicinity of the device or its site of use Warning Read all safety warnings and all instructions Failure to follow the warnings and instructions may result in electric shock fire and or serious injury Save all warnings and instructions for future reference This appliance can be used by children aged from 8 ...

Страница 3: ... refrigerant is odourless Only install the device in compliance with the national installation regulations Observe the national gas regulations Only install operate and store the device PAC 3500 X in a room measuring more than 14 m2 Store the device in a way that no mechanical damage can occur Please note that the connected ducts must not contain any sources of ignition R290 is a refrigerant that ...

Страница 4: ...plode if heated P210 Keep away from heat sparks open flames and other ignition sources No smoking P377 Leaking gas fire Do not extinguish unless leak can be stopped safely P410 P403 Protect from sunlight Store in a well ventilated place Warning of electrical voltage Work on the electrical components must only be carried out by an authorised specialist company Warning of electrical voltage Before a...

Страница 5: ...he device operates fully automatically and features a variety of further options The device can for instance be switched on or off automatically with time delay via the timer function Operation of the device is possible either via the control panel at the device or via the supplied infrared remote control The device was designed for universal and flexible application Due to its compact dimensions ...

Страница 6: ...evice Hold onto the mains plug while pulling the power cable out of the mains socket When the device is not being used observe the following storage conditions Only store the device in a room measuring more than 14 m2 dry and protected from frost and heat in an upright position where it is protected from dust and direct sunlight with a cover to protect it from invasive dust if necessary Place no f...

Страница 7: ...nection free Make sure that no curtains or other objects interfere with the air flow Inserting the air filter Note Do not operate the device without an inserted air filter Without an air filter the inside of the device will be heavily contaminated which could reduce the dehumidification performance and result in damage to the device Make sure that the air filters are installed before switching the...

Страница 8: ...t air hose can also be hooked into a tilted window For this purpose we recommend using a window seal optional Install the exhaust air hose inclined with the air direction The connected hose must not contain any source of ignition Example with exhaust air hose For installing the exhaust air hose please observe the following 30 cm 150 cm Avoid kinks and bends in the exhaust air hose as they would le...

Страница 9: ... Designation Meaning 15 Water filling level LED Empty condensation tray indication 16 ON OFF button Switching the device on and off 17 Compressor operation LED Indication of compressor operation in cooling mode 18 MODE button Selecting the operating mode automatic operation cooling dehumidification ventilation 19 Operating mode LEDs Indicates the selected operating mode automatic operation cooling...

Страница 10: ...ling 19 fan speed 27 and possibly compressor operation 17 are illuminated When combining automatic operation and ventilation the desired fan speed may be set using the SPEED button 26 ð At an ambient temperature of 25 C the device automatically switches over to fan operation The LEDs for automatic operation 19 ventilation 19 and fan speed 27 are illuminated When combining automatic operation and v...

Страница 11: ... cap and rubber stopper for later use 5 Connect the condensation drain hose to the hose connection 13 6 Guide the other hose end to a suitable drain or sufficiently dimensioned collection container To ensure that the condensate can run off the condensation drain hose must not be kinked nor should it have to overcome an uphill incline towards the drain Ventilation Info Remove the exhaust air hose d...

Страница 12: ...fined time the device switches itself off Notes regarding automatic switch off Pressing the ON OFF button 16 deactivates the automatic switch off function Night mode Night mode can only be activated in cooling mode Night mode comes with the following settings After one hour the preset temperature is increased by 1 C After 2 hours the preset temperature will again be increased by 1 C Then the tempe...

Страница 13: ...pressor has tripped Disconnect the device from the mains and let it cool down for approx 10 minutes before reconnecting it Check whether the ambient temperature equals the target temperature in cooling mode The compressor will not switch on unless the respective temperature is reached The compressor may start up with a delay of 3 minutes as it is provided with an internal protection against direct...

Страница 14: ...on tray and drain hose X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and clean if necessary Clean the exterior Visually check the inside of the device for dirt Check the air filter for dirt and foreign objects and clean or replace if necessary Replace the air filter...

Страница 15: ...ble safety signs Cleaning the housing Clean the housing with a soft damp and lint free cloth Ensure that no moisture enters the housing Protect electrical components from moisture Do not use any aggressive cleaning agents such as cleaning sprays solvents alcohol based or abrasive cleaners to dampen the cloth Visual inspection of the inside of the device for dirt 1 Remove the air filter 2 Use a tor...

Страница 16: ...ng cap and rubber stopper from the condensate outlet 3 Drain the condensate 4 Reinsert the rubber stopper in the condensate outlet and reattach the sealing cap Ensure the tight fit of the rubber stopper for otherwise there might be uncontrolled water leakage ð The water filling level LED 15 will go out as soon as the condensate has been drained Activities required after maintenance If you want to ...

Страница 17: ...350 m3 h Mains supply 220 240 V 50 Hz Nominal current 5 7 A Power input cooling operation 1 28 kW Sound pressure level at a distance of 1 m 57 dB A Refrigerant R290 Amount of refrigerant 300 g GWP factor 3 CO2 equivalent 0 0009 t Dimensions length x width x height 313 x 480 x 744 mm Minimum distance to walls and other objects top A rear B sides C front D 50 cm 50 cm 50 cm 50 cm Weight 26 kg Remote...

Страница 18: ...18 EN local air conditioner PAC 3500 X Circuit diagram ...

Страница 19: ...9 local air conditioner PAC 3500 X Overview and lists of spare parts Note The position numbers of the spare parts differ from those describing the positions of other parts mentioned in this operating manual ...

Страница 20: ...DE 1 111 REMOTE CONTROL RECEIVER 1 134 RUBBER STOPPER 1 112 FILTER FRAME FOR EVAPORATOR 1 135 DRAIN KNOB 1 113 SIDE FILTER FRAME 2 136 DRAIN TUBE 1 114 FILTER FRAME FOR CONDENSER 1 137 7 SUPPORTER FOR TEMPERATURE SENSOR 1 115 WATER CASE 1 138 SUPPORTER TO FIX WIRES 1 116 BASE PANEL 1 139 LEAKPROOF RUBBER STOPPER 1 117T DOWN FUNNEL A 1 140 EXHAUST PIPE 1 117B DOWN FUNNEL B 1 141 ADAPTOR 1 118T UP F...

Страница 21: ... FOR TOP AIR CHANNEL 1 408 SUCTION TUBE FOR CONDENSER 1 303 SUPPORTER FOR THE PUMP MOTOR 2 409 DISCHARGING TUBE FOR CONDENSOR 1 304 MAIN SUPPORTER 1 410 3 WAY VALVE 1 306 CASTER 4 411 REFRIGERANT CHARGING TUBE 1 307 SUPPORTER TO FIX FAN BLADE FOR MOTOR 1 412 DRYER 1 308 FIN GND 1 413 CAPILLARY 1 310 SCREWDRIVER 1 415 THERMAL SLEEVE 1 401 CONDENSOR 1 416 SLEEVE FOR CAPILLARY 1 402 EVAPORATER 1 417 ...

Страница 22: ...ment aims to enable the re use recycling and other forms of recovery of waste equipment as well as to prevent negative effects for the environment and human health caused by the disposal of hazardous substances potentially contained in the equipment Have the refrigerant propane disposed of appropriately and according to the national regulations by a company with the relevant certification European...

Страница 23: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com ...

Отзывы: