background image

9

EN

Operating manual – dehumidifier / climate manager DH 30 VPR+ / DH 60 VPR+

Here a worst-case scenario:

A modern car wet with rain is parked in a garage along with a
classic vehicle. The room temperature is 4 °C. Attributable to
evaporation of water at the still warm, wet vehicle, the relative
humidity in the garage quickly rises to 95 %.

95 % of relative humidity at 

4 °C

 mean that in absolute terms

only about 

6 g of water

 are bound in a cubic metre of air, for

that is the physical limit that can be absorbed.

For comparison:

At a room temperature of 

21 °C

 and 95 % RH, 

17 g of water

are retained by a cubic metre of air. In other words, for every
100 m³ of room air in the garage the air contains over 1 litre
more of pure water (than at 4 °C) in the form of water vapour.
This quickly adds up to several litres of water in the garage! And
it results in the DH-VPR+ withdrawing next to none of the water
from the room air at these low temperatures, because it is
unable to extract any. Hardly any water is bound in the room air,
rendering dehumidification a physical impossibility.

The higher the room temperature, the more moisture

can be absorbed by the room air

Temperature in the
garage:

4 °C

21 °C

Relative humidity:

50 %

95 %

50 %

95 %

Moisture retained
by the room air:

(absolute humidity)

3 g/m³

6 g/m³

9 g/m³ 17 g/m³

Vapour pressure

difference:

3 g/m³

Vapour pressure

difference:

8 g/m³

Consequence for
drying wet
vehicles:

Low drying speed

(minor vapour pressure

difference)

High drying speed

(great vapour pressure

difference)

With 95 % the relative humidity given in our example is rather
high. The vehicle's corrosion and the mould formation at the
walls started immediately. It does not take a great amount of
absolute humidity in the air to get the processes of corrosion
and mould growth going. It is enough if water is bound as
vapour, even though expressed in absolute terms (g/m³) the
values are not very impressive.

And there is another aspect:

Due to the minor absolute vapour pressure differences, the
drops of water on the wet car do not evaporate. It stays wet
despite the DH-VPR+ operation. And the situation is the same:
Low temperatures --> minor differences in the air's moisture
content with regard to the absolute humidity level (g/m³) in spite
of large differences regarding the relative humidity.
Even at low temperatures, the DH-VPR+ keeps the room climate
at the desired level. If new water enters the scene at these low
room temperatures by way of a wet vehicle and the temperature
remains low, the wet vehicle will dry very slowly, hence causing
the humidity inside and at the car to rise to a corrosion-prone
level. Dry keeping is not a problem. Quick drying, however, is a
physical impossibility.

Conclusion:

Using DH-VPR+ devices classic cars can be stored and
showcased during the winter to a temperature of 0 °C. Yet the
capacity is disproportionately reduced (see table 

Correlation

between the temperature in the garage and duration of the
drying process

).

However, if both the storage and a quick drying of wet vehicles
are required – also during the winter – you will additionally have
to ensure heating in order to increase the drying rate for wet
vehicles so as to effectively prevent corrosion and mould
growth.
So, if the classic car garage is used all through the year and / or
there are often wet cars inside, we recommend room
temperatures of at least 15 °C. If water only sporadically enters
the garage, there is no need for permanent heating. It will be
sufficient to heat the garage to a level between 15 °C and 20 °C
during the drying phase lasting several days. On these grounds,
we recommend a general on-demand heating option to achieve
a reasonable temperature for drying the garage quickly.
Depending on the temperature, a heating phase of 3 to 7 days
should normally suffice to ensure a fail-safe drying process.
This period can be considerably reduced by the use of fans.
Especially for a quick drying in the car body, at the underbody
as well as in ribbings and hollows we always recommend the
use of fans for wet classic cars (see table 

Correlation between

the temperature in the garage and duration of the drying
process

).

The more frequently and extensively the cars are used, the
higher should be the average temperature in the garage so as to
attain a quick and fail-safe drying process and thus to prevent
corrosion and mould.

Содержание DH 30 VPR+

Страница 1: ...TRT BA DH30VPR DH60VPR TC 002 EN DH 30 VPR DH 60 VPR EN OPERATING MANUAL DEHUMIDIFIER CLIMATE MANAGER ...

Страница 2: ... This signal word indicates a hazard with an average risk level which if not avoided can result in serious injury or death Caution This signal word indicates a hazard with a low risk level which if not avoided can result in minor or moderate injury Notice This signal word indicates important information e g material damage but does not indicate hazards Info Information marked with this symbol help...

Страница 3: ...cket Observe the technical data when selecting extensions to the power cable Completely unroll the extension cable Avoid electrical overload Before carrying out maintenance care or repair work on the device remove the mains plug from the mains socket Hold onto the mains plug while doing so Switch the device off and disconnect the power cable from the mains socket when the device is not in use Do n...

Страница 4: ...Warning A falling device can cause injuries Always transport and assemble the device with the help of other persons Never stand below the device when it is suspended Ensure adequate stability of the device s wall fixing Warning Risk of suffocation Do not leave the packaging lying around Children may use it as a dangerous toy Warning Ozone formation In case of improper use the device generates a mi...

Страница 5: ...r thus conditioned mixes with the air in the room via the air outlet 1 The humidity in the room where the device is positioned is reduced as air constantly circulates through the device Depending on the air temperature and the relative humidity the condensed water either drops into the condensation tray continuously or only during the defrost phases To set the desired humidity level a hygrostat wi...

Страница 6: ...vice 8 Control dial hygrostat tamper proof installation inside the device DH 60 VPR 1 2 6 3 7 8 5 6 6 4 Scope of delivery Dehumidifier Wall holder Air filter combination filter Air filter standard Condensation drain hose ø 5 mm inside l 10 m Power cable with CEE 7 7 Schuko plug Operating manual Available accessories Combination filter DH 30 VPR 5 pieces art no 7 710 000 926 Standard air filter DH ...

Страница 7: ...etely unrolled Insert the mains plug into a properly secured mains socket When assembling the device observe the minimum distance from adjacent walls or other objects as described in the Technical Data chapter C C A B D Assembly Assemble the device as follows Select screw and dowel sizes suitable for the weight of the device see technical data and the structure of the wall Warning A falling device...

Страница 8: ...y means of the mounting brackets Utilize the help of one or two other persons as well as suitable lifting gear to do so 9 Put the housing back on the device 10 Fasten the housing to the device Storage Drain any possibly remaining condensate When the device is not being used observe the following storage conditions in an upright and stable position dry and protected from frost and heat protected fr...

Страница 9: ...an be reduced through additional ventilation starting at 19 C less than 1 day drying accelerated by approx 50 70 16 19 C approx 1 day 12 15 C 1 2 days 8 11 C 3 5 days drying accelerated by approx 30 50 4 7 C more than 5 days The time for drying moisture accumulated in the car body at the underbody and inside the engine compartment as well as in ribbings and hollows could even be significantly exte...

Страница 10: ...peration And the situation is the same Low temperatures minor differences in the air s moisture content with regard to the absolute humidity level g m in spite of large differences regarding the relative humidity Even at low temperatures the DH VPR keeps the room climate at the desired level If new water enters the scene at these low room temperatures by way of a wet vehicle and the temperature re...

Страница 11: ...al correlations are illustrated elaborately by way of example scenarios and the recommended course of action Operating elements Info You can access the operating elements by opening the filter flap at the device see chapter Maintenance The control panel of the DH 30 VPR is located on the left hand side in case of the DH 60 VPR it can be found on the right The depiction of the operating elements fe...

Страница 12: ...dours and monitoring the humidity level ð If the set humidity level is exceeded the compressor will automatically be activated to dehumidify the room air once again Automatic defrost If the room temperature is lower than 15 C the heat exchanger will freeze during dehumidification The device will then carry out an automatic defrost The duration of the defrost process can vary depending on the room ...

Страница 13: ... intensive treatment at level 5 to effectively eliminate the cause 1 Make sure that all surfaces in the room to be treated are freely accessible for the circulatory air of the DH VPR open windows boot and bonnet of vehicles open wardrobe doors shut the curtains to provide the best possible effective surface If possible remove car mats and carpets in the passenger compartment and boot and spread th...

Страница 14: ...he brickwork Individual odour perception The odour perception and rating differs from one individual to another Because of this individual perception a general across the board recommendation for dosage and usage is not feasible therefore every user can only achieve his odour balance by actively and patiently levelling out the intensity levels Whether it concerns the smell of mould in a vault cell...

Страница 15: ...e achieve a satisfactory solution in 99 of cases with extreme fuel odours Often another separate ionizer can also be helpful in such cases Please contact our consultants as needed Air filter As standard devices of the VPR series are delivered with 2 air filters 1 x air filter dust standard 1 x air filter dust soot combination filter The technical data given for the air volume freely blowing refers...

Страница 16: ...rmation regarding the dehumidification performance and drying rate Ensure that the relative humidity complies with the technical data see chapter Important information regarding the dehumidification performance and drying rate Check the preselected humidity level at the hygrostat s control dial 8 The humidity in the room must be above the selected range Reduce the desired humidity level by turning...

Страница 17: ...e condensation tray 6 If so clean the drain hoses 7 Put the housing back on the device 8 Fasten the housing to the device 9 Plug the power cable back into the mains socket If the alarm signal continues despite these measures please contact Trotec The device gets very warm is loud or loses power Check the air filter for dirt Remove external dirt Check the inside of the device for dirt If necessary ...

Страница 18: ... every 2 months at the latest Empty the condensate pump condensation tray and or condenser dryer X Maintenance and care log Device type Device number Maintenance and care interval 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Check air inlets and outlets for dirt and foreign objects and clean if necessary Clean the exterior Visually check the inside of the device for dirt Check for damage Check the attac...

Страница 19: ...eaning the housing Clean the device with a soft damp and lint free cloth Ensure that no moisture enters the housing Protect electrical components from moisture Do not use any aggressive cleaning agents such as cleaning sprays solvents alcohol based or abrasive cleaners to dampen the cloth Cleaning the inside of the device Perform this activity once a year 1 Open the screw connection at the housing...

Страница 20: ... and edges of the air filter must not be deformed or rounded Before reinserting the air filter make sure that it is undamaged and dry Notice A dirty air filter obstructs the air current This can lead to damages at the refrigerant circuit and ionizer During operation with a dirty air filter there will be neither dehumidification nor ionization 1 Open the filter flap 3 3 2 Remove the air filter 3 In...

Страница 21: ...lative humidity 30 to 60 RH Max permissible relative humidity 90 RH Max pump height of the condensate pump 10 m 15 m Condensation drain hose ø 5 mm inside l 10 m Weight 57 kg 90 kg Dimensions width x depth x height incl wall holder 787 x 280 x 690 mm 1 255 x 280 x 690 mm Standard faceplate steel white powder coated Minimum distance to walls or other objects A top B bottom C side D front 12 5 cm 12...

Страница 22: ...21 EN Operating manual dehumidifier climate manager DH 30 VPR DH 60 VPR Refrigerant circuit diagram COMPRESSOR SOLENOID VALVE AIR CONDENSER EVAPORATOR DRIER CAPILLARY INSULATION PROCESS PORT ...

Страница 23: ...e www trotec24 com The separate collection of waste electrical and electronic equipment aims to enable the re use recycling and other forms of recovery of waste equipment as well as to prevent negative effects for the environment and human health caused by the disposal of hazardous substances potentially contained in the equipment You are responsible for deleting any personal data stored on the wa...

Страница 24: ...Trotec GmbH Co KG Grebbener Str 7 D 52525 Heinsberg 49 2452 962 400 49 2452 962 200 info trotec com www trotec com ...

Отзывы: