WWW.AWC608.COM
2) Find the actual installation position of each limit switch
separately. When it is sensed by general manual, see whether the
limit switch corresponding to the test interface has changed
not(first: Is it from 1 to 0 or 0 to 1, second : Is it the limit of the
corresponding axis), if there is a change, the limit installation is
normal.
If No change:
1) Please check whether the line of the limit switch of the
corresponding axis is connecte
2) After checking the wiring, check whether the limit switch is good
or not.
3) If the limit switch is good, it is possible that the wiring board is
bad. Directly ground or disconnect the input port. Enter and check
the test input port interfa
no change means the wiring board is bad. Othetwise, If there is a
change, the wiring board is OK, so you can be sure that the limit
switch is bad.
3. After the previous tests have determined that all input ports
good, the input port status is displayed according to the interface
The limit pole of the corresponding axis displayed as "1" is set
negative, and the input port is set to low level effective
The limit polarity of the corresponding axis displayed as "
positive, and the input port is set to high level effective
4. After all input ports confirm the setting is OK, then power off.
3: Test whether the required OUT port is connected
Motion controller user manual
2) Find the actual installation position of each limit switch
separately. When it is sensed by general manual, see whether the
limit switch corresponding to the test interface has changed
not(first: Is it from 1 to 0 or 0 to 1, second : Is it the limit of the
corresponding axis), if there is a change, the limit installation is
1) Please check whether the line of the limit switch of the
corresponding axis is connected correctly,
2) After checking the wiring, check whether the limit switch is good
3) If the limit switch is good, it is possible that the wiring board is
bad. Directly ground or disconnect the input port. Enter and check
the test input port interface, and if the corresponding input port has
no change means the wiring board is bad. Othetwise, If there is a
change, the wiring board is OK, so you can be sure that the limit
3. After the previous tests have determined that all input ports
good, the input port status is displayed according to the interface
The limit pole of the corresponding axis displayed as "1" is set
negative, and the input port is set to low level effective
The limit polarity of the corresponding axis displayed as "
positive, and the input port is set to high level effective
4. After all input ports confirm the setting is OK, then power off.
3: Test whether the required OUT port is connected
TC-6832
Motion controller user manual
36
2) Find the actual installation position of each limit switch
separately. When it is sensed by general manual, see whether the
limit switch corresponding to the test interface has changed or
not(first: Is it from 1 to 0 or 0 to 1, second : Is it the limit of the
corresponding axis), if there is a change, the limit installation is
1) Please check whether the line of the limit switch of the
2) After checking the wiring, check whether the limit switch is good
3) If the limit switch is good, it is possible that the wiring board is
bad. Directly ground or disconnect the input port. Enter and check
ce, and if the corresponding input port has
no change means the wiring board is bad. Othetwise, If there is a
change, the wiring board is OK, so you can be sure that the limit
3. After the previous tests have determined that all input ports are
good, the input port status is displayed according to the interface
The limit pole of the corresponding axis displayed as "1" is set
The limit polarity of the corresponding axis displayed as "0" is set
4. After all input ports confirm the setting is OK, then power off.