background image

Spellbind

4

Meter

Incoming

supply

fuse

Meter

tails

Consumer

unit

Pull cord

isolating switch

Shower

unit

Fuse or

MCB

RCD

(can be part of

consumer unit)

80A or 100A

main switch

Shepperton Park,

Triton Road, Nuneaton,

Warwickshire, CV11 4NR

Table A

MCB

30/32A

32A
40A
40A
40A

40/45A

45A

cartridge

fuse

30A
35A
35A
45A
45A
45A
45A

unit 

rating

7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW

10.5kW

CIRCUIT PROTECTION

Fig.4

 Schematic of installation circuit

E-002-A

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

 

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, it 
is advisable to contact the local electricity 
supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

  

Before making any sort of electrical 

connection within the installation make sure 
that no terminal is live. If in any doubt, 
switch off the whole installation at the mains 
supply and remove the correct fuse.

3

 

The shower must be connected to its own 
independent electrical circuit. IT MUST NOT 
be connected to a ring main, spur, socket 
outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.4).

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 
installation will not be straightforward and 
may require a new consumer unit serving 
the house or just the shower.

4.2

 You will need to contact the local electricity 

company. They will check the supply and 
carry out what is necessary. 

5

 

For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably rated 
Miniature Circuit Breaker (MCB) or cartridge 
fuse 

(see Table A).

5.1

  A 30mA residual current device (RCD) must 

be installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily 
accessible to switch off after using the 
shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B).

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the 

disconnection time and thermal constraints 
which means that for any given combination 
of current demand, voltage drop and cable 
size, there is a maximum permissible circuit 
length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed in 
areas where the ambient temperature is 
above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

 

In the majority of installations, the cable 
will unavoidably be placed in one or more 
of the above conditions. This being so, it 
is strongly recommended to use a 
minimum of 10mm cabling throughout 
the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Electrical requirements

E-002-A

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 
protection must conform with BS 7671 (IEE 
wiring regulations) and be sufficient for the 
amperage required.
The following notes are for guidance only:

1

 

The shower must only be connected to a 
230-240V ac supply. If you are installing a 
shower with a kilowatt rating above 9kW, it 
is advisable to contact the local electricity 
supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

  

Before making any sort of electrical 

connection within the installation make sure 
that no terminal is live. If in any doubt, 
switch off the whole installation at the mains 
supply and remove the correct fuse.

3

 

The shower must be connected to its own 
independent electrical circuit. IT MUST NOT 
be connected to a ring main, spur, socket 
outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 
has a main switch rating of 80A or above 
and that it has a spare fuse way which will 
take the fuse or Miniature Circuit Breaker 
(MCB) necessary for the shower 

(Fig.4).

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 
installation will not be straightforward and 
may require a new consumer unit serving 
the house or just the shower.

4.2

 You will need to contact the local electricity 

company. They will check the supply and 
carry out what is necessary. 

5

 

For close circuit protection DO NOT use a 
rewireable fuse. Instead use a suitably rated 
Miniature Circuit Breaker (MCB) or cartridge 
fuse 

(see Table A).

5.1

  A 30mA residual current device (RCD) must 

be installed in all UK electric and pumped 
shower circuits. This may be part of the 
consumer unit or a separate unit.

6

 

A 45 amp double pole isolating switch with 
a minimum contact gap of 3 mm in both 
poles must be incorporated in the circuit.

6.1

  It must have a mechanical indicator showing 

when the switch is in the OFF position, and 
the wiring must be connected to the switch 
without the use of a plug or socket outlet.

6.2

  The switch must be accessible and clearly 

identifiable, but out of reach of a person 
using a fixed bath or shower, except for the 
cord of a cord operated switch, and should 
be placed so that it is not possible to touch 
the switch body while standing in a bath or 
shower cubicle. It should be readily 
accessible to switch off after using the 
shower.

7

 

Where shower cubicles are located in any 
rooms other than bathrooms, all socket 
outlets in those rooms must be protected by 
a 30mA RCD.

8

 

The current carrying capacity of the cable 
must be at least that of the shower circuit 
protection 

(see Table B).

8.1

  To obtain full advantage of the power 

provided by the shower, use the shortest 
cable route possible from the consumer unit 
to the shower.

8.2

  It is also necessary to satisfy the 

disconnection time and thermal constraints 
which means that for any given combination 
of current demand, voltage drop and cable 
size, there is a maximum permissible circuit 
length.

9

 

The shower circuit should be separated from 
other circuits by at least twice the diameter 
of the cable or conduit.

9.1

  The current rating will be reduced if the 

cabling is bunched with others, surrounded 
by thermal loft or wall insulation or placed in 
areas where the ambient temperature is 
above 30°C. Under these conditions, 
derating factors apply and it is necessary to 
select a larger cable size.

9.2

 

In the majority of installations, the cable 
will unavoidably be placed in one or more 
of the above conditions. This being so, it 
is strongly recommended to use a 
minimum of 10mm cabling throughout 
the shower installation.

9.3

  In any event, it is essential that individual 

site conditions are assessed by a competent 
electrician in order to determine the correct 
cable size and permissible circuit length.

Fig.3

W-006-A

WARNING!

THIS APPLIANCE MUST BE EARTHED

Содержание Spellbind

Страница 1: ...Installation and operating instructions Spellbind thermostatic electric shower T00334 2180409H November 2011 Installers please note these instructions are to be left with the user...

Страница 2: ...ioning 14 Operating the shower 16 Operating functions 19 Cleaning the showerhead 21 Instructions for installers and service engineers only 22 Spare parts 24 Fault finding 26 27 Water Cable entry point...

Страница 3: ...ld also cause the Pressure Relief Device in the unit to operate This product is not suitable for mounting into steam rooms or steam cubicles PLUMBING The plumbing installation must comply with Water R...

Страница 4: ...engineer to determine the nature of the fault and replace the safety device once the unit has been repaired This book contains all the necessary fitting and operating instructions for your Triton Spel...

Страница 5: ...connector 8 Terminal block 9 Earth connection 10 PRD 11 Solenoid valve 12 Trim plate 13 Thermostatic valve 14 Scale trap 15 Pressure switch 16 Shower outlet 17 Guide pockets Inside cover fig 2 18 Cont...

Страница 6: ...se of a plug or socket outlet 6 2 The switch must be accessible and clearly identifiable but out of reach of a person using a fixed bath or shower except for the cord of a cord operated switch and sho...

Страница 7: ...aximum permissible circuit length 9 The shower circuit should be separated from other circuits by at least twice the diameter of the cable or conduit 9 1 The current rating will be reduced if the cabl...

Страница 8: ...e to achieve optimum performance from the unit throughout the year For guidance on the running and static pressures contact the local Water Authority or consult a competent plumber Under site conditio...

Страница 9: ...tray then a double check valve or similar must be fitted in the supply pipework to prevent back flow Liquid Crystal Display This shower unit has a LCD which has an optimum viewing angle that is slight...

Страница 10: ...nit is not blocked fig 7 When commissioning the showerhead must be removed from the flexible hose Failure to follow this procedure may cause the PRD to operate Make sure the shower is positioned over...

Страница 11: ...try points will invalidate product approvals If bottom surface entry is required then the necessary hole will need to be cut out in the thinned section of the trimplate using a junior hacksaw and file...

Страница 12: ...d Screw the top left hand fixing screw into position leaving the base of the screw head protruding 6 mm out from the wall Hook the backplate over this screw then fit the other two fixing screws into p...

Страница 13: ...water supply long enough to clear the debris to waste Procedure Turn off the water supply either at the mains stopvalve or the isolating stopvalve Connect the mains water supply to the inlet fig 12 o...

Страница 14: ...e The supply cable earth conductor must be sleeved fig 14 The outer sheath of the supply cable must be stripped back to the minimum The supply cable must be secured either by routing through conduit o...

Страница 15: ...backplate and check the wires are not trapped Guide into position so that the control spindle locates correctly the flats ensure the spindle and knob will only fit one way While applying slight press...

Страница 16: ...n fig 17 c Make sure the temperature control knob on the cover is rotated to 12 o clock the knob flat inside the cover should be uppermost fig 18 d Carefully locate the cover tags into the guide pocke...

Страница 17: ...he water flow Unscrew the cover retaining screws again and lift the cover from the backplate Attached to the control PCB inside the cover is a 14 way ribbon cable The ribbon cable connector must be pl...

Страница 18: ...light fig 22 It will remain in this standby mode until the shower is started To start the shower Press the START STOP button and water will flow The display shows FUL fig 23 indicating full power is b...

Страница 19: ...decreases to try to achieve the same temperature as before Note if the setting was high at full power then it will not be possible to obtain the same temperature on economy power The shower will try...

Страница 20: ...30 shows maximum temperature position all segments alight that corresponds to the temperature control To decrease the shower temperature Turn the temperature control anti clockwise the current tempera...

Страница 21: ...r you clean the showerhead or not The shower will then reset automatically for a further preset number of shower operations before flashing the reminder again Low pressure When the display backlight t...

Страница 22: ...t of abnormal operation which could cause unsafe temperatures within the unit the device will disconnect the heating elements It will require a visit from a qualified engineer to determine the nature...

Страница 23: ...This movement may turn the cartridge assembly as well until it reaches a stop Hold the cartridge firmly and continue to twist anti clockwise Having loosened the sprayplate it can be unscrewed and remo...

Страница 24: ...person SWITCH OFF THE ELECTRICITY SUPPLY AT THE MAINS Remove the cover The inlet filter is situated in the solenoid inlet fig 38 and can be removed to clean Remove the trimplate and disconnect and re...

Страница 25: ...discharging as the heater can exhausts Clean out the trap and remove all sediment Flush the can through by leaving the cap off and switching on the power at the isolating switch Note Make sure the wat...

Страница 26: ...ssure Relief Device 82800450 7 Trimplate 7053323 8 Can brace 7053008 9 Thermostatic valve and O rings 4 83307130 10 Connecting tube 22010260 11 Scale trap cover c w O rings and screw 83307140 12 Displ...

Страница 27: ...ode gravity showerhead white 22011070 chrome 22011110 gold 22011120 17 5 mode kwik kleen electric showerhead white 22011270 chrome 22011250 18 Flexible hoses are available in the following sizes 1 00...

Страница 28: ...itch 1 1 1 Blown fuse or circuit breaker Check supply Renew or reset fuse or circuit breaker If it fails again consult a qualified electrician 1 1 2 Power cut Check other appliances and if necessary c...

Страница 29: ...1 Debris in solenoid 8 1 Blocked showerhead 8 2 Twisted blocked flexible shower hose 8 3 Showerhead not removed whilst commissioning 7 1 1 Contact Customer Service for advice 8 1 1 Clean or replace bl...

Страница 30: ...Spellbind 28 Entry Points Diagram Key Water Entry Points Cable Entry Points...

Страница 31: ...cy under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659 All our electric products are labe...

Страница 32: ...ting of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Service Advisor will arrange for a qualified engineer to call 3 A...

Отзывы: