IVORY 4 electric shower

4

W-006-A

WARNING!

THIS APPLIANCE MUST BE EARTHED

Meter

Incoming

supply

fuse

Meter

tails

Consumer

unit

Pull cord

isolating switch

Shower

unit

Fuse or

MCB

RCD

(can be part of

consumer unit)

80A or 100A

main switch

Table A

MCB

30/32A

32A
40A
40A
40A

40/45A

45A

cartridge

fuse

30A
35A
35A
45A
45A
45A
45A

unit 

rating

7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW

10.5kW

CIRCUIT PROTECTION

Fig.4

 Schematic of installation circuit

ELECTRICAL REQUIREMENTS

The installation, supply cable and circuit 

protection must conform with BS 7671 (IEE 

wiring regulations) and be sufficient for the 

amperage required.

The following notes are for guidance only:

1

 

The shower must only be connected to a 

230-240V ac supply. If you are installing a 

shower with a kilowatt rating above 9kW, it 

is advisable to contact the local electricity 

supply company.

1.1

  The electrical rating of the shower is shown 

on the rating label 

(Fig.3)

 within the unit.

2

 

 Before making any sort of electrical 

connection within the installation make 

sure that no terminal is live. If in any doubt, 

switch off the whole installation at the mains 

supply and remove the correct fuse.

3

 

The shower must be connected to its own 

independent electrical circuit. 

IT MUST NOT

 

be connected to a ring main, spur, socket 

outlet, lighting circuit or cooker circuit.

3.1

  The electrical supply must be adequate for 

the loading of the unit and existing circuits.

4

 

Check your consumer unit (main fuse box) 

has a main switch rating of 80A or above 

and that it has a spare fuse way which will 

take the fuse or Miniature Circuit Breaker 

(MCB) necessary for the shower 

(Fig.4)

.

4.1

  If your consumer unit has a rating below 

80A or if there is no spare fuse way, then the 

installation will not be straightforward and 

may require a new consumer unit serving 

the house or just the shower.

4.2

  You will need to contact the local electricity 

company. They will check the supply and 

carry out what is necessary. 

  For close circuit protection 

DO NOT

 use a 

rewireable fuse. Instead use a suitably rated 

Miniature Circuit Breaker (MCB) or cartridge 

fuse 

(see Table A)

.

5.1

  A 30mA residual current device (RCD) 

MUST

 be installed in all UK electric and 

pumped shower circuits. This may be part of 
the consumer unit or a separate unit.

Triton Showers,

Triton Road, Nuneaton,

Warwickshire, CV11 4NR

xxxx

Fig.3

Содержание IVORY 4

Страница 1: ...Installers please note these instructions are to be left with the user 2180775H April 2012 Installation and operating instructions IVORY 4 electric shower...

Страница 2: ...ing connections 11 Electrical connections 12 Replacing the cover 12 13 Commissioning 14 Operating the shower 15 16 Operating functions 17 Cleaning 17 Instructions for installers and service engineers...

Страница 3: ...and could also cause the PRD Pressure Relief Device in the unit to operate 1 9 This product is not suitable for mounting into steam rooms or steam cubicles 2 PLUMBING 2 1 The plumbing installation mus...

Страница 4: ...rate at a constant rate at your chosen power setting It is the rate of the water passing through the heater can which determines the water temperature The slower the flow the hotter the water becomes...

Страница 5: ...ising valve 6 Solenoid valve 7 Can and element assembly 8 Thermal cut out TCO 9 Earth connection 10 Outlet pipe 11 Start Stop micro switch Pressure relief device see page 20 Cover fig 2 12 Ivory 4 fro...

Страница 6: ...bt switch off the whole installation at the mains supply and remove the correct fuse 3 The shower must be connected to its own independent electrical circuit IT MUST NOT be connected to a ring main sp...

Страница 7: ...dy while standing in a bath or shower cubicle It should be readily accessible to switch off after using the shower 7 Where shower cubicles are located in any rooms other than bathrooms all socket outl...

Страница 8: ...es per minute the inlet of the shower for full performance for 7 5Kw 8 5Kw 9 5Kw Minimum running pressure and flow to 150kPa 1 5 bar at 11 litres per minute the inlet of the shower for full performanc...

Страница 9: ...showerhead be constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill over level of the relevant bath shower tray or other fixed...

Страница 10: ...t to remove them Lift the cover from the backplate Entry Points Water Left Bottom Back and Top Right Bottom Back Cable Left Bottom Back and Top The water inlet fig 7 has been designed to allow left or...

Страница 11: ...ide if top or bottom pipe entry is required Once chosen carefully remove the appropriate cut out using a junior hacksaw and file Please note NONE of the cut outs are designed as snap out entry points...

Страница 12: ...the backplate are shown in fig 10 Drill and plug the wall An appropriate drill bit should be used If the wall is brick plasterboard or a soft building block appropriate wall plugs and screws should b...

Страница 13: ...the shower flush out the pipework to remove all swarf and system debris This can be achieved by connecting a hose to the pipework and turning on the mains water supply long enough to clear the debris...

Страница 14: ...ply cable must be secured either by rout ing through conduit or in trunking or by embed ding in the wall in accordance with current IEE regulations The use of connections within the unit to supply pow...

Страница 15: ...turn the stabi liser valve spindle fully clockwise until resistance is felt fig 14 4 With the cover off the shower turn the tem perature control so that it goes to Maximum HOT fig 16 c Make sure the...

Страница 16: ...he control to MINIMUM FLOW may cause the PRD to operate 2 Turn on the electric and mains water supplies to the shower 3 Turn the power selector to the COLD setting fig 18 and wait until water starts t...

Страница 17: ...ot be met due to low water pressure it will be necessary to operate the unit on this setting during the warmer months because of flow rate limitations entering the unit The symbol is a high power sett...

Страница 18: ...s advisable to be certain that the showering temperature is satisfactory by testing with your hand before stepping under the showerhead There will always be a time delay of a few seconds between selec...

Страница 19: ...will disconnect the heating elements It will require a visit from a qualified engineer to determine the nature of the fault and replace the safety device once the unit has been repaired TP Temperatur...

Страница 20: ...electricity supply and water supply at the mains The inlet filter is situated in the bottom of the inlet pipe fig 20 To gain access to the filter remove the cover and then unscrew the assembly from t...

Страница 21: ...ch Module P22611003 5 Can Assembly 8 5kW 83314800 Can Assembly 9 5kW 83314810 Can Assembly 10 5kW 83314820 6 Outlet Pipe and PRD S23511002 7 Terminal Block wires S82201240 8 Thermal Cut Out TCO 220123...

Страница 22: ...educe flow rate via temperature control Is water supply mains or tank fed If tank fed replumb to mains water supply or see 4 2 4 If mains fed make sure that the mains stopvalve is fully open and there...

Страница 23: ...4 2 4 4 3 1 4 3 2 4 4 1 5 1 1 6 1 1 6 2 1 6 3 1 6 4 1 7 1 1 7 2 1 7 3 1 required see rating label Reduction in ambient water temperature Electrical malfunction or safety cut out operated Water pressu...

Страница 24: ...IVORY 4 electric shower 22 Entry Points Diagram Key Water Entry Points Cable Entry Points...

Страница 25: ...IVORY 4 electric shower 23...

Страница 26: ...IVORY 4 electric shower 24...

Страница 27: ...nt Agency under the following schemes Repic Producers take back scheme PTS registration number WEE EJ3466QV Valpak Distributor take back scheme DTS registration number 9659 All our electric products a...

Страница 28: ...your details including post code the model number and power rating of the product together with the date of purchase and where applicable details of the particular fault 2 If required the Customer Se...

Отзывы: