background image

Herrmidicool

I n s t a l l a t i o n ,   O p e r a t i o n   &   M a i n t e n a n c e   M a n u a l

4

www.trioniaq.com

I. INTRODUCTION

The Herrmidicool system is an in-duct air/water atomization 
system designed to introduce atomized water into the 
airstream. The unit uses a native BACnet controller that 
responds to an analog 0-5 VDC demand signal to start the 
humidification process. An input for proving airflow prior to 
starting the system is provided as well as alarm indication.  
The touchscreen display allows the operator to interact with 
the system. Network communications are available to allow 
system monitoring and control.

II. OPERATIONAL CHARACTERISTICS

Upon an increase in demand signal above 20%, the controls 

will energize the compressed air solenoid valve.  An air 

pressure switch will close if sufficient air pressure is present 

to allow for proper atomization.  When the air pressure switch 

contacts close, the water solenoid valve will energize and 

atomization will begin.  Each nozzle is equipped with a clean 

out pin that helps keep the water orifice clear of mineral build-

up each time the nozzle is cycled.  Periodically, the controls 

will de-energize the water solenoid valve in order to actuate 

the  clean-out  pin  to  keep  the  water  orifice  clear.    During 

operation if the air proving switch contacts open, the system 

will stop.  If the system on/off switch is opened the system 

will stop.  See the Controls section for additional details.

Allowable Operating Conditions

Ambient Temperature: 40°-120°F (4°-50°C)

Ambient Relative Humidity: 0% - 90%

Line Voltage: -15% to +10% Nominal

Frequency: 50/60 Hz

Supply Air Pressure: 60-200 psig

Supply Air Quality: Filter clean and dry to 35°F dewpoint.

Supply Water Temperature: 40°-100°F (4°-38°C)

Supply Water Pressure: 50-100 psig

Supply Water TDS less than 50 ppm: Consult Factory 

with water analysis and application data prior to selecting 

equipment.

NOTE: If units are mounted in outdoor enclosures, conditions 

inside enclosure must be maintained as listed above. 

III. MOUNTING

The Herrmidicool system consists of two basic components: 

the control cabinet and the atomizing-head manifold 

assembly. The control cabinet should be mounted so that the 

water outlet of the control cabinet is level or below the water 

manifold in the air handler. Air vents must be mounted on 

any loops necessary to connect the cabinet to the manifolds.

Minimum Cabinet Clearances:

Top: 1” Bottom: 12”

Sides: 2” Front: 4”

32” Working Area Clearance

Hang the cabinet on the wall or unistrut mounting frame. 

Two keyhole slots and two additional mounting holes are 

provided. Be sure the unit is level and mounted directly 

to the wall to wood studs as least 2” thick (or equivalent). 

The atomizing head manifolds consisting of air manifolds, 

atomizing heads, water manifold and unistrut brackets are to 

be located as shown on specific layout drawings with each 

job.  Typically,  a  “unistrut”  style  mounting  structure  is  field 

fabricated to support the atomizing manifold.

Manifold Installation:

1. Install the air/water manifolds per the layout drawing 

included with this package.

2. Use only copper, plastic or stainless steel piping as 

specified in your print package.

3. Keep runs between control cabinets and heads as short 

as possible.

4. Piping runs between control cabinets and manifolds 

should be as direct as possible. If loops are unavoidable, 

automatic air vents must be supplied and installed.

IV. PLUMBING

Each cabinet has an air inlet, water inlet, air outlet(s), water 

outlet(s) and a drain. All air connections are ½” and all water 

connections, including drain, are ½”. 

1. Drain loop must extend 3” above highest location of 

heads or water outlet port on cabinet. This loop allows water 

pressure to be relieved on system shutdown.

2. Piping from control cabinet to manifolds without draining 

should be ¾” for the air and ½” for the water piping unless 

otherwise shown on your job specific drawings provided for 

your project.

Содержание HERRMIDIFIER Herrmidicool

Страница 1: ...T R I O N w w w t r i o n i a q c o m Herrmidicool Installation Operation Maintenance READ SAVE THESE INSTRUCTIONS...

Страница 2: ...ion 4 II Operational Characteristics 4 III Mounting 4 IV Plumbing 4 V Controls 5 VI Control Board Operation 5 VII Start up Checklist 6 VIII Start up 7 IX Atomizing Head Operation 7 X Pressure Settings...

Страница 3: ...OROUGHLY BEFORE INSTALLING OR SERVICING THE UNIT DANGER OF BURNS THE HUMIDIFIER CONTAINS HIGH TEMPERATURE COMPONENTS AND DELIVERS STEAM AT 100 C 212 F ATTENTION READ THIS MANUAL FACTORY INSTALLED OPTI...

Страница 4: ...ata prior to selecting equipment NOTE If units are mounted in outdoor enclosures conditions inside enclosure must be maintained as listed above III MOUNTING The Herrmidicool system consists of two bas...

Страница 5: ...as inside of comers Air proving devices should be mounted so that they sense airflow or the absence of it Wire the device so that it closes when airflow is present and will open when there is no airfl...

Страница 6: ...GING SOME OF THESE SETTINGS MAY RENDER THE FACTORY WARRANTY VOID When touching SETUP or MODULE STATUS the administrator will be prompted for a password Enter 2222 to log in to the controller Network s...

Страница 7: ...settings at any other time The instructions below assume that the atomizing heads are installed at the same elevation as the water control section Adjustment from this standard must be made to compens...

Страница 8: ...reign matter may be restricting water flow in the water nozzle AH 942 Turn off the air and water valves at the head Remove the atomizer nozzle and water nozzle Blow water nozzle with air Do not use wi...

Страница 9: ...Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union Nut AH 20SS...

Страница 10: ...i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 10 www trioniaq com XVI WIRING DIAGRAM WARNING Absolutely no other components may be mounted inside or electrically tapped into the humidifie...

Страница 11: ...Herrmidicool I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www trioniaq com THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No 269604 001 Rev 06 18...

Отзывы: