background image

Herrmidicool

I n s t a l l a t i o n ,   O p e r a t i o n   &   M a i n t e n a n c e   M a n u a l

8

www.trioniaq.com

XIV. NOZZLE TROUBLESHOOTING

A. Heavy spray pattern (droplets too large)

1. All heads – This is caused by incorrect air and water 

pressure settings. Review settings and adjust as required. 

Never allow air pressure to exceed the water pressure.

2. Individual Heads – These heads are not getting enough 

air for one of the following reasons:

a. Foreign matter may be clogging the screen (AH-21) in 

the air strainer union of the head. Clean or replace it.

b. One or more of the heads may have been improperly 

adjusted or the individual shut-off valve may be throttled. 

No valves should ever be throttled. Readjust if necessary.

c. Water nozzle (AH-942) orifice may have been enlarged 

due to bent cleaning needle. Replace parts as required.

d.  Atomizer  nozzle  (AH-941)  orifice  may  have  been 

enlarged due to improper cleaning or dirty air. Replace 

part as required. Standard air orifice sizes for the various 

heads are as follows.

6 lbs/hr

0.95 mm

8 lbs/hr

1.10 mm

10 lbs/hr

1.15 mm

12 lbs/hr

1.35 mm

15 lbs/hr

1.45 mm

B. Spray pattern too light at full capacity 

1. All heads – This is caused by incorrect air and water 

pressure settings. Review settings and adjust as required. 

Never allow air pressure to exceed the water pressure.

2. Individual heads – These heads are not getting enough 

water for one of the following reasons:

a. One or more of the heads may have been improperly 

adjusted or the individual shut-off valve may be throttled. 

No valves should ever be throttled.

b.  Foreign  matter  may  be  restricting  water  flow  in  the 

water nozzle (AH-942). Turn off the air and water valves 

at the head.

Remove the atomizer nozzle and water nozzle. Blow 

water nozzle with air. Do not use wire or other hard 

object that will score the inside of the nozzle.

C. Sputtering heads – air pressure at the atomizing heads 

exceeds water pressure.

1. Adjust air and water pressures to correct operating 

pressures.

2. Normally open drain solenoid on water control section 

may have a malfunction allowing water to leak into drain 

line during operation. Solenoid valve seat may have 

foreign matter under the seat causing it to leak. Solenoid 

may have defective seat.

D. Inoperative heads (all heads)

1. The atomizing heads may be shutdown because the 

system controls and setpoints are satisfied.

2. If the desired RH level has not been achieved, check 

calibration of the controls and adjust as required.

3. Air and water supply valves are not open.

4. No supply air pressure. If supply valves are open and 

the gauges indicate no air pressure, check compressed 

air source.

5. No power to the air and water solenoid valves. Check 

controls and control cabinet fuses.

Individual heads

6. Be sure air and water valves to the atomizing heads 

are open.

7. Possible defective parts inside atomizing head. Shut-off 

air and water valves to the head and remove head from the 

system. Disassemble and examine internal parts. Repair 

and reassemble as required. Rebuilding kits are available 

from your local TRION/HERRMIDIFIER representative. 

Perform a complete restart and readjustment of the 

atomizing head upon reassembly and repair.

E. Air Without Water – Be sure water valve to control 

section is open. Check modulating water valve, water 

solenoid and drain solenoid on water control section.

Содержание HERRMIDIFIER Herrmidicool

Страница 1: ...T R I O N w w w t r i o n i a q c o m Herrmidicool Installation Operation Maintenance READ SAVE THESE INSTRUCTIONS...

Страница 2: ...ion 4 II Operational Characteristics 4 III Mounting 4 IV Plumbing 4 V Controls 5 VI Control Board Operation 5 VII Start up Checklist 6 VIII Start up 7 IX Atomizing Head Operation 7 X Pressure Settings...

Страница 3: ...OROUGHLY BEFORE INSTALLING OR SERVICING THE UNIT DANGER OF BURNS THE HUMIDIFIER CONTAINS HIGH TEMPERATURE COMPONENTS AND DELIVERS STEAM AT 100 C 212 F ATTENTION READ THIS MANUAL FACTORY INSTALLED OPTI...

Страница 4: ...ata prior to selecting equipment NOTE If units are mounted in outdoor enclosures conditions inside enclosure must be maintained as listed above III MOUNTING The Herrmidicool system consists of two bas...

Страница 5: ...as inside of comers Air proving devices should be mounted so that they sense airflow or the absence of it Wire the device so that it closes when airflow is present and will open when there is no airfl...

Страница 6: ...GING SOME OF THESE SETTINGS MAY RENDER THE FACTORY WARRANTY VOID When touching SETUP or MODULE STATUS the administrator will be prompted for a password Enter 2222 to log in to the controller Network s...

Страница 7: ...settings at any other time The instructions below assume that the atomizing heads are installed at the same elevation as the water control section Adjustment from this standard must be made to compens...

Страница 8: ...reign matter may be restricting water flow in the water nozzle AH 942 Turn off the air and water valves at the head Remove the atomizer nozzle and water nozzle Blow water nozzle with air Do not use wi...

Страница 9: ...Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union Nut AH 20SS...

Страница 10: ...i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 10 www trioniaq com XVI WIRING DIAGRAM WARNING Absolutely no other components may be mounted inside or electrically tapped into the humidifie...

Страница 11: ...Herrmidicool I n s t a l l a t i o n O p e r a t i o n M a i n t e n a n c e M a n u a l 11 www trioniaq com THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 12: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No 269604 001 Rev 06 18...

Отзывы: