The A-33 assembly (Figure 3) is a single head assembly for 

use in restricted areas.

Control Sections

The control sections provide the following features:

•  Regulate plant air and water to desired operating pressures

•  Monitor  the  flow  of  air  and  water  to  the  heads  via 

solenoid valves

•  Air pressure switch prevents flow of water to heads until 

there is sufficient air pressure for atomization

•  Dripless operation and automatic purging of minerals 

from heads during system cycling

The standard air control sections are available in two 

different sizes, and the water control section is available in 

one size (see pages 6-7).

Minimum Pipe 

Size to Heads

Size

Pipe 

Connections

Max. 

Capacity

Air

Water

Water 

Drain

1/2”

1/2” FPT

240 lbs/hr

3/4”

1/2”

1/2”

3/4”

3/4” FPT Air

1/2” FPT Water

500 lbs/hr

3/4”

1/2”

1/2”

Controls

The standard Dual Pneumatic atomizing system requires 

ON-OFF humidistats for operation.  Controls may be 

provided by others, in which case, consultation with TRION 

is essential to ensure proper operation.

Several control options are available from TRION.  The 

standard system consists of a control humidistat and high-

limit (safety) humidistat.  (A hygrometer is optional with any 

Dual Pneumatic system.)

For critical applications where extreme tolerances or 

temperature and humidity requirement demand it, an 

electronic humidistat may be required.

Air Supply

Plant air can be used if supply is adequate.  All heads use 

12 SCFM of air per 100 pounds of atomized water delivered.  

However, a safety factor of 20% should be added for line losses.

Air should run through a minimum of a cyclone type moisture 

separator  and  a  0.5  micron  coalescing  filter  (supplied  by 

others) to ensure that it is dry and oil-free before it reached 

the air control section and the heads.

An  air  compressor  used  only  for  humidification  can  be 

operated at 60-70 psi.  No need to run at 125-150 psi, as 

this would waste energy.

Water Supply

With any air/water atomization system, any solids in the 

water will be distributed into the air during atomization.  

Always check the water quality before installing an air/water 

atomization system.  TRION, or your local lab, can perform 

this test for you.  The Dual Pneumatic atomizing system is 

available for raw and demineralized water supplies.  With 

your water analysis, you and your TRION/HERRMIDIFIER 

representative can determine what, if any, water treatment 

is required.

Figure 2. B-13 Head Assembly

Figure 3. A-33 Head Assembly

Содержание Heremidifier Dual Pneumatic

Страница 1: ...T R I O N w w w t r i o n i a q c o m Dual Pneumatic Atomizing System READ SAVE THESE INSTRUCTIONS...

Страница 2: ...matter must be flushed from air and water lines supplying the atomizing heads before the head valves are opened and heads used If foreign matter reaches the interior of the heads each head must be dis...

Страница 3: ...ncidental expenses such as cost of transporting the part unit to TRION shall be borne by the user Upon completion of the reconditioning the humidifier will be returned at no cost to the user In an eff...

Страница 4: ...se immediately preventing any chance of dripping or spitting At the end of each cycle the air pressure is allowed to fall gradually to zero through the heads blowing all water from the mixing chamber...

Страница 5: ...dard system consists of a control humidistat and high limit safety humidistat A hygrometer is optional with any Dual Pneumatic system For critical applications where extreme tolerances or temperature...

Страница 6: ...v i c e M a n u a l 6 www trioniaq com Figure 4 AH 1020 Air Control Section For System Capacities up to 240 lbs hr Approximate Measurements 23 L x 6 H Figure 5 AH 1050 Air Control Section For System C...

Страница 7: ...PRIMARY PRESSURE REGULATOR SECONDARY PRESSURE REGULATOR 1 2 NPT FEMALE DRAIN LOOP CONNECTION DRAIN LOOP MUST EXTEND MINIMUM OF 3 ABOVE ATOMIZING HEADS DRAIN LOOP SUPPLIED BY OTHER n THREE WAY WATER V...

Страница 8: ...ds in a manner where the spray will contact a wall machine unit heater pipes columns conveyer lights wires or obstructions Distance from such obstructions should not be less than the maximum visible s...

Страница 9: ...e height of the heads because the pressure readings at the control sections and heads will differ 3 Always be sure the drain from the 3 way solenoid extends a minimum of 3 above the heads pipe run or...

Страница 10: ...dure for the water line Clean lines to all control sections as described above 4 CHECK ELECTRICAL WIRING OF CONTROLS Set the SAFETY humidistat to maximum Set the CONTROL humidistat to 20 NOTE If only...

Страница 11: ...es and necessitate bleeding of lines Repeat procedure on all control sections and primary reducers Normally with all heads operating it will be necessary to again adjust the primary water pressure red...

Страница 12: ...ray pattern adequate At least ONCE A YEAR remove the atomizer nozzles AH 941 X X Clean these nozzles in a weak acid solution Do NOT use a wire or other object that will score the nozzle or its orifice...

Страница 13: ...quired Use a dependable psychrometer 3 Air and water valves serving the control section are not open 4 Electric current not flowing to central section Check wiring and supply lines 5 Compressed air is...

Страница 14: ...ell as the RH indicator with a dependable psychrometer and adjust as required 3 Be sure humidistat is not being influenced by a hot air stream blowing directly on it Correct as required EXCESSIVE AIR...

Страница 15: ...t 253208 001 Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union...

Страница 16: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 16 www trioniaq com X TYPICAL LAYOUTS...

Страница 17: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 17 www trioniaq com XI WIRING DIAGRAMS...

Страница 18: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No AH 22 Rev 06 18...

Отзывы: