background image

Dual Pneumatic

I n s t a l l a t i o n ,   O p e r a t i o n   &   S e r v i c e   M a n u a l

4

www.trioniaq.com

II. SYSTEM OPERATION

The Dual Pneumatic atomizing system operates with air and 

water under pressure - air at approximately 30 psi and water 

at approximately 32 - 38 psi.  Air consumption is figured at 

.12 SCFM per lbs. of water atomized per hour.  A safety 

factor of 20% should be added for any potential line losses.

Operation is fully automatic and controlled by humidistats.  

When the relative humidity (RH) level drops below the 

setting on the control humidistat, the contacts on the control 

humidistat close the circuit, opening the solenoid valve on the 

air control section.  As soon as pressure builds up sufficiently 

to atomize, the air pressure switch closes the circuit to the 

water solenoid valve, starting water flow.  Water can not flow 

without adequate air pressure.  All valves close if there is a 

power failure.  The water solenoid will close if there is an air 

compressor failure.

When the desired level of RH is reached, the humidistat 

breaks the circuit, and all solenoid valves close, shutting 

off flow of air and water to the heads.  The three-way water 

solenoid bleeds off the water pressure instantly, allowing the 

water valve seat in the head to close immediately, preventing 

any chance of dripping or spitting.  At the end of each cycle, 

the air pressure is allowed to fall gradually to zero through 

the heads, blowing all water from the mixing chamber of the 

heads.  The stainless steel cleaning needle connected to the 

diaphragm cleans the water orifice of the heads at the end 

of each ON cycle.  By completely drying the mixing chamber 

of each head, mineral build-up is prevented.  This cleaning 

is so effective that YEARLY maintenance is typically all that 

is required!

III. SYSTEM COMPONENTS

A Dual Pneumatic atomizing system consists of atomizing 

nozzles, control sections, humidistats, and an adequate air 

and water supply.

Atomizing Heads

Atomizing heads are available in capacities of 6, 8, 10, 12, or 

15 lbs. of water per hour.  

The proper head capacity for a given project is selected on 

the basis of installed height of the head above the floor, clear 

area available for spray patterns to evaporate, and conditions 

to be maintained in the humidified space.

Atomizing head assemblies are available in three versions.

The 

A-17 assembly

 (Figure 1) consists of two identical 

capacity heads spraying in opposite directions and is 

used when areas are clear of obstacles in both directions 

and where distances shown in installation section can be 

observed.

The 

B-13 assembly

 (Figure 2) consists of two identical 

capacity head assemblies discharging in the variable 

directions of discharge.

Figure 1. A-17 Head Assembly

Содержание Heremidifier Dual Pneumatic

Страница 1: ...T R I O N w w w t r i o n i a q c o m Dual Pneumatic Atomizing System READ SAVE THESE INSTRUCTIONS...

Страница 2: ...matter must be flushed from air and water lines supplying the atomizing heads before the head valves are opened and heads used If foreign matter reaches the interior of the heads each head must be dis...

Страница 3: ...ncidental expenses such as cost of transporting the part unit to TRION shall be borne by the user Upon completion of the reconditioning the humidifier will be returned at no cost to the user In an eff...

Страница 4: ...se immediately preventing any chance of dripping or spitting At the end of each cycle the air pressure is allowed to fall gradually to zero through the heads blowing all water from the mixing chamber...

Страница 5: ...dard system consists of a control humidistat and high limit safety humidistat A hygrometer is optional with any Dual Pneumatic system For critical applications where extreme tolerances or temperature...

Страница 6: ...v i c e M a n u a l 6 www trioniaq com Figure 4 AH 1020 Air Control Section For System Capacities up to 240 lbs hr Approximate Measurements 23 L x 6 H Figure 5 AH 1050 Air Control Section For System C...

Страница 7: ...PRIMARY PRESSURE REGULATOR SECONDARY PRESSURE REGULATOR 1 2 NPT FEMALE DRAIN LOOP CONNECTION DRAIN LOOP MUST EXTEND MINIMUM OF 3 ABOVE ATOMIZING HEADS DRAIN LOOP SUPPLIED BY OTHER n THREE WAY WATER V...

Страница 8: ...ds in a manner where the spray will contact a wall machine unit heater pipes columns conveyer lights wires or obstructions Distance from such obstructions should not be less than the maximum visible s...

Страница 9: ...e height of the heads because the pressure readings at the control sections and heads will differ 3 Always be sure the drain from the 3 way solenoid extends a minimum of 3 above the heads pipe run or...

Страница 10: ...dure for the water line Clean lines to all control sections as described above 4 CHECK ELECTRICAL WIRING OF CONTROLS Set the SAFETY humidistat to maximum Set the CONTROL humidistat to 20 NOTE If only...

Страница 11: ...es and necessitate bleeding of lines Repeat procedure on all control sections and primary reducers Normally with all heads operating it will be necessary to again adjust the primary water pressure red...

Страница 12: ...ray pattern adequate At least ONCE A YEAR remove the atomizer nozzles AH 941 X X Clean these nozzles in a weak acid solution Do NOT use a wire or other object that will score the nozzle or its orifice...

Страница 13: ...quired Use a dependable psychrometer 3 Air and water valves serving the control section are not open 4 Electric current not flowing to central section Check wiring and supply lines 5 Compressed air is...

Страница 14: ...ell as the RH indicator with a dependable psychrometer and adjust as required 3 Be sure humidistat is not being influenced by a hot air stream blowing directly on it Correct as required EXCESSIVE AIR...

Страница 15: ...t 253208 001 Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union...

Страница 16: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 16 www trioniaq com X TYPICAL LAYOUTS...

Страница 17: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 17 www trioniaq com XI WIRING DIAGRAMS...

Страница 18: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No AH 22 Rev 06 18...

Отзывы: