background image

Dual Pneumatic

I n s t a l l a t i o n ,   O p e r a t i o n   &   S e r v i c e   M a n u a l

10

www.trioniaq.com

Loss of Water Pressure Due to Friction

in psi per 100 ft. of Type “K” copper tube at 60 PSIG

Flow Gals. 

per Min.

Pipe Size

1/2”

3/4”

1”

1 1/4” 1 1/2”

2”

1

1.30

0.25

0.05

-

-

-

2

4.50

0.85

0.23

0.07

-

-

3

9.00

1.70

0.45

0.15

0.063

-

4

15.00

2.80

0.75

0.25

0.10

-

5

22.00

4.20

1.10

0.36

0.16

0.042

6

31.00

5.80

1.50

0.50

0.22

0.058

7

40.00

7.50

2.00

0.65

0.28

0.073

For longer or shorter lengths of pipe,the friction loss is 

proportional to the length.

Example:     AIR LINE            500 ft.     One half of the above

 

 

                4,000 ft.     Four times the above

 

      WATER LINE       50 ft.     One half the above

 

 

 

     400 ft.      Four times the above

5.  Follow start-up procedure EXACTLY.  Repeat the start-up 

procedure every time the system is drained or cleaned.

V. START-UP PROCEDURES

1.  CHECK INSTALLATION WITH THE LAYOUT 

DRAWING.  

Be sure that the equipment has been 

installed exactly as laid out on the system drawing 

- location of head assemblies, control sections, 

humidistats, etc. and that the proper size pipe has 

been used on all air and water supply lines as well as 

drain lines.  (Frictional losses and pressure drops were 

considered in making the layout.)

2.  CLOSE ALL AIR AND WATER VALVES AT EACH 

HEAD ASSEMBLY.

  It is vitally important that no foreign 

matter in the supply lines - air and water - gets into the 

heads.

3.  CLEAN MAIN SUPPLY LINES TO CONTROL 

SECTIONS.  

Close air and water valves on the incoming 

side of all control sections.  Start the air compressor.  

Open the main valves at the air compressor and water 

source.  Break the unions just ahead of the incoming air 

and water pressure gauges of the control sections.  AIR 

MAIN LINE: Put on safety glasses.  Place a cloth over the 

open air line to catch any flying debris.  Place a bucket 

over the end of the air line.  Slowly open the valve and 

let the air line blow until clean.  DO NOT LOOK INTO 

THE BUCKET WHILE THE AIR IS BLOWING.  Close the 

valve and retighten the union securely.  WATER MAIN 

LINE: Repeat the above procedure for the water line.  

Clean lines to all control sections as described above.

4.  CHECK ELECTRICAL WIRING OF CONTROLS.  

Set 

the SAFETY humidistat to maximum.  Set the CONTROL 

humidistat to 20%.  NOTE: If only one humidistat is used, 

set to 20% or switch it to OFF.  Open air valve ONLY to 

feed air to control section.  Do NOT open water valve.  

to properly sense the relative humidity of the surrounding air. 

(See Wiring Diagram on page 17.)

Other Considerations

1.  Air must be free of oil and water.  It is wise to place filters 

on both the air and water feed lines ahead of the control 

sections.  TRION recommends the use of a moisture 

separator and trap and a coalescing filter on the air line.

2.  To prevent condensation on uncovered cold water pipes 

in the system, it is advisable to consider using aftercooler 

water  from  the  air  compressor  in  the  humidification 

system.  If this is not practical, a heater for the system’s 

water supply may be used.

3.  If  the  water  supply  pressure  fluctuates  and  doesn’t 

maintain 50 psi at the highest level of a head assembly, 

it will be necessary to supply a water pressure booster 

pump or bladder tank for the system.  Consult TRION for 

assistance in sizing pump and tank.

4.  With extremely large systems, supply piping should be 

sized as follows:

System Cap. - Water MIN. Water System Req. - Air

Min. Air

Up to 1,000 lbs/hr

1/2”

10 - 24 CFM

3/4”

1,000 to 2,000 lbs/hr

3/4”

24 - 45 CFM

1”

2,000 - 3,000 lbs/hr

1”

45 - 70 CFM

1 1/4”

Over 3,000 lbs/hr

1 1/4”

70 - 100 CFM

1 1/2”

Supply piping should be sized to control sections so as to 

minimize pressure drop in accordance with table below.

Cu. Ft. Free 

Air per Min.

Pipe Size

1/2”

3/4”

1”

1 1/4” 1 1/2”

2”

10

6.50

0.99

0.28

-

-

-

20

23.90

3.90

1.31

0.25

0.11

-

30

58.50

9.01

2.51

0.57

0.26

-

40

-

16.00

4.45

1.03

0.46

-

50

-

25.10

6.96

1.61

0.71

0.19

60

-

36.20

10.00

2.32

1.02

0.28

70

-

49.30

13.70

3.16

1.40

0.37

80

-

64.50

17.80

4.14

1.83

0.49

90

-

82.80

22.00

5.23

2.32

0.62

100

-

-

27.90

6.47

2.86

0.77

125

-

-

48.60

10.20

4.49

1.19

150

-

-

62.80

14.20

6.43

1.72

175

-

-

-

19.80

8.72

2.38

200

-

-

-

25.80

11.40

3.06

250

-

-

-

40.40

17.90

4.78

300

-

-

-

58.20

25.80

6.85

350

-

-

-

-

35.10

9.36

400

-

-

-

-

45.80

12.10

450

-

-

-

-

58.00

15.40

500

-

-

-

-

71.60

19.20

Loss of Air Pressure Due to Friction

in psi per 1000 ft of pipe at 100 PSIG

Содержание Heremidifier Dual Pneumatic

Страница 1: ...T R I O N w w w t r i o n i a q c o m Dual Pneumatic Atomizing System READ SAVE THESE INSTRUCTIONS...

Страница 2: ...matter must be flushed from air and water lines supplying the atomizing heads before the head valves are opened and heads used If foreign matter reaches the interior of the heads each head must be dis...

Страница 3: ...ncidental expenses such as cost of transporting the part unit to TRION shall be borne by the user Upon completion of the reconditioning the humidifier will be returned at no cost to the user In an eff...

Страница 4: ...se immediately preventing any chance of dripping or spitting At the end of each cycle the air pressure is allowed to fall gradually to zero through the heads blowing all water from the mixing chamber...

Страница 5: ...dard system consists of a control humidistat and high limit safety humidistat A hygrometer is optional with any Dual Pneumatic system For critical applications where extreme tolerances or temperature...

Страница 6: ...v i c e M a n u a l 6 www trioniaq com Figure 4 AH 1020 Air Control Section For System Capacities up to 240 lbs hr Approximate Measurements 23 L x 6 H Figure 5 AH 1050 Air Control Section For System C...

Страница 7: ...PRIMARY PRESSURE REGULATOR SECONDARY PRESSURE REGULATOR 1 2 NPT FEMALE DRAIN LOOP CONNECTION DRAIN LOOP MUST EXTEND MINIMUM OF 3 ABOVE ATOMIZING HEADS DRAIN LOOP SUPPLIED BY OTHER n THREE WAY WATER V...

Страница 8: ...ds in a manner where the spray will contact a wall machine unit heater pipes columns conveyer lights wires or obstructions Distance from such obstructions should not be less than the maximum visible s...

Страница 9: ...e height of the heads because the pressure readings at the control sections and heads will differ 3 Always be sure the drain from the 3 way solenoid extends a minimum of 3 above the heads pipe run or...

Страница 10: ...dure for the water line Clean lines to all control sections as described above 4 CHECK ELECTRICAL WIRING OF CONTROLS Set the SAFETY humidistat to maximum Set the CONTROL humidistat to 20 NOTE If only...

Страница 11: ...es and necessitate bleeding of lines Repeat procedure on all control sections and primary reducers Normally with all heads operating it will be necessary to again adjust the primary water pressure red...

Страница 12: ...ray pattern adequate At least ONCE A YEAR remove the atomizer nozzles AH 941 X X Clean these nozzles in a weak acid solution Do NOT use a wire or other object that will score the nozzle or its orifice...

Страница 13: ...quired Use a dependable psychrometer 3 Air and water valves serving the control section are not open 4 Electric current not flowing to central section Check wiring and supply lines 5 Compressed air is...

Страница 14: ...ell as the RH indicator with a dependable psychrometer and adjust as required 3 Be sure humidistat is not being influenced by a hot air stream blowing directly on it Correct as required EXCESSIVE AIR...

Страница 15: ...t 253208 001 Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union...

Страница 16: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 16 www trioniaq com X TYPICAL LAYOUTS...

Страница 17: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 17 www trioniaq com XI WIRING DIAGRAMS...

Страница 18: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No AH 22 Rev 06 18...

Отзывы: