background image

Dual Pneumatic

I n s t a l l a t i o n ,   O p e r a t i o n   &   S e r v i c e   M a n u a l

13

www.trioniaq.com

Replace parts as required.

4.  Atomizer  nozzle  (AH-941-X-X)  orifice  may  have  been 

enlarged due to improper cleaning or dirty air.  (See 

Maintenance section.)  Replace parts as required.

SPRAY PATTERN TOO LIGHT

ALL HEADS served by one control section: either this is 

caused by too high a setting on the air pressure regulator of 

the air control section, which calls for slightly decreasing the 

air pressure - or too low a setting on the water regulator of 

the water control section, which requires increasing the water 

setting slightly.

INDIVIDUAL HEADS: Heads are not getting enough water.

1.  Water valve at head may have been throttled.  No valves 

should ever be throttled!  Adjust head and shown in Step 

7 of start-up procedure.

2.  Foreign matter may be restricting water flow in the water 

nozzle (AH-942-X).  Shut off air and water valves at head 

assembly.  Remove atomizer nozzle (AH-941-X-X) and 

water nozzle (AH-942-X) with wrench.  DO NOT use wire 

or hard object that will score inside.

SPUTTERING HEADS

ALL HEADS served by one control section: air pressure at 

heads exceeds water pressure at heads.

•  Adjust air and/or water pressure at control section so that 

air pressure is about 2 psi lower than water pressure.

•  Three-way solenoid on water control section may be 

malfunctioning to allow water to leak down drain port 

when system is operating.  This may be caused by dirt 

under the drain valve seat or a bad valve seat on the 

drain side of the three-way solenoid.  NOTE: The drain 

side of the three-way solenoid should open only when 

the system shuts off.  Approximately one cup of water 

should be drained from the system between cycles.  A 

greater amount may be a sign of air trapped in the water 

line.  Review start up procedure.

INDIVIDUAL HEADS:

1.  Water valve supplying head assembly has been throttled.  

No valves should ever be throttled.

2.  Head improperly adjusted.  Follow Step 7 of start-up 

procedure.

3.  Part malfunctioning inside head.  Check diaphragm (AH-

10), spring (AH-8), and valve disk (AH-16).  Correct as 

required.

INOPERATIVE HEADS (No air or water)

ALL HEADS served by one control section:

1.  These heads shut down because control humidistat is 

satisfied.

2.  If proper RH level has not been attained, check calibration 

of the control humidistat and adjust if required.  Use a 

dependable psychrometer.

3.  Air and water valves serving the control section are not 

open.

4.  Electric  current  not  flowing  to  central  section.    Check 

wiring and supply lines.

5.  Compressed air is not reaching the control section.  

Possible compressor failure.

INDIVIDUAL HEADS:

1.  Be sure air and water valves at head assembly are 

fully open.

2.  Indicates diaphragm (AH-10) may be ruptured or 

leaking OR water and air ports clogged.  Close air and 

water valves at head assembly.  Remove rear part of 

head (Bonnet, 253209-00X) with a wrench.  Examine 

the diaphragm (AH-10), spring (AH-7), and valve disc 

(AH-16).  Replace any bad parts.  If these parts are 

OK, reassemble the head.  CAUTION: Use care in 

reassembling so that cleaning needle is not damaged.  

Remove atomizer nozzle (AH-941-X-X) and water nozzle 

(AH-942-X).  Clean these nozzle ports with air pressure 

or as recommended under maintenance.  DO NOT use 

a wire or any object that will score the inside or port of 

the nozzles.  Reassemble the head, open the air valve 

of the head assembly, then the water valve of the head 

assembly and adjust spray pattern.  (See Step 7 of the 

start-up procedure.)

AIR WITHOUT WATER

ALL HEADS served by one control section: be sure water 

valve at control section is open.  RH exceeds that set on the 

SAFETY humidistat.  This shuts off water to all heads but 

allows air to flow.  Correct this condition by:

1.  Set SAFETY humidistat higher than CONTROL 

humidistat.

2.  Make sure CONTROL humidistat is functioning to start 

and stop system.

3.  Check calibration of BOTH humidistats with a dependable 

psychrometer.

4.  Check the setting on the air pressure switch and be sure 

that the switch is cutting in at 26 psi and out at 20 psi of 

air pressure.  Adjust accordingly by setting high end first 

at 26 psi and then turning low end up against it.

INDIVIDUAL HEADS:

1.  Water cut-off at valve at head assembly.

2.  Water nozzle (AH-942-X) plugged with foreign matter.  

Correct as above under “Spray Pattern Too Light”.

HUMIDITY LEVEL TOO LOW

1.  Be sure CONTROL humidistat is set at desired RH.

2.  Check calibration of CONTROL humidistat and 

HUMIDITY INDICATOR with dependable psychrometer 

and adjust as required.

3.  Be sure humidistat is not being “influenced” by the spray 

pattern of a head coming too close to it.  Correct as 

required.

4.  Be sure humidistat is not being “influenced” by a cold air 

stream blowing directly on it.  Correct as required.

5.  The temperature of the air in the area being humidified 

may be different for than that for which the system was 

designed.  If so, AND this changed temperature will now 

Содержание Heremidifier Dual Pneumatic

Страница 1: ...T R I O N w w w t r i o n i a q c o m Dual Pneumatic Atomizing System READ SAVE THESE INSTRUCTIONS...

Страница 2: ...matter must be flushed from air and water lines supplying the atomizing heads before the head valves are opened and heads used If foreign matter reaches the interior of the heads each head must be dis...

Страница 3: ...ncidental expenses such as cost of transporting the part unit to TRION shall be borne by the user Upon completion of the reconditioning the humidifier will be returned at no cost to the user In an eff...

Страница 4: ...se immediately preventing any chance of dripping or spitting At the end of each cycle the air pressure is allowed to fall gradually to zero through the heads blowing all water from the mixing chamber...

Страница 5: ...dard system consists of a control humidistat and high limit safety humidistat A hygrometer is optional with any Dual Pneumatic system For critical applications where extreme tolerances or temperature...

Страница 6: ...v i c e M a n u a l 6 www trioniaq com Figure 4 AH 1020 Air Control Section For System Capacities up to 240 lbs hr Approximate Measurements 23 L x 6 H Figure 5 AH 1050 Air Control Section For System C...

Страница 7: ...PRIMARY PRESSURE REGULATOR SECONDARY PRESSURE REGULATOR 1 2 NPT FEMALE DRAIN LOOP CONNECTION DRAIN LOOP MUST EXTEND MINIMUM OF 3 ABOVE ATOMIZING HEADS DRAIN LOOP SUPPLIED BY OTHER n THREE WAY WATER V...

Страница 8: ...ds in a manner where the spray will contact a wall machine unit heater pipes columns conveyer lights wires or obstructions Distance from such obstructions should not be less than the maximum visible s...

Страница 9: ...e height of the heads because the pressure readings at the control sections and heads will differ 3 Always be sure the drain from the 3 way solenoid extends a minimum of 3 above the heads pipe run or...

Страница 10: ...dure for the water line Clean lines to all control sections as described above 4 CHECK ELECTRICAL WIRING OF CONTROLS Set the SAFETY humidistat to maximum Set the CONTROL humidistat to 20 NOTE If only...

Страница 11: ...es and necessitate bleeding of lines Repeat procedure on all control sections and primary reducers Normally with all heads operating it will be necessary to again adjust the primary water pressure red...

Страница 12: ...ray pattern adequate At least ONCE A YEAR remove the atomizer nozzles AH 941 X X Clean these nozzles in a weak acid solution Do NOT use a wire or other object that will score the nozzle or its orifice...

Страница 13: ...quired Use a dependable psychrometer 3 Air and water valves serving the control section are not open 4 Electric current not flowing to central section Check wiring and supply lines 5 Compressed air is...

Страница 14: ...ell as the RH indicator with a dependable psychrometer and adjust as required 3 Be sure humidistat is not being influenced by a hot air stream blowing directly on it Correct as required EXCESSIVE AIR...

Страница 15: ...t 253208 001 Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union...

Страница 16: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 16 www trioniaq com X TYPICAL LAYOUTS...

Страница 17: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 17 www trioniaq com XI WIRING DIAGRAMS...

Страница 18: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No AH 22 Rev 06 18...

Отзывы: