background image

Dual Pneumatic

I n s t a l l a t i o n ,   O p e r a t i o n   &   S e r v i c e   M a n u a l

11

www.trioniaq.com

Adjust air pressure regulator of control section to 30 psi.  

Slowly move the CONTROL humidistat to a higher RH 

until you hear a “click” indicating the 2-way solenoid valve 

on the air control section has opened.  NOTE: If only one 

humidistat is used, follow above procedure slowly raising 

RH setting, or if switch is used, turn to ON.  Reduce the 

setting on the SAFETY humidistat until you hear a click 

indicating the 3-way solenoid on the water line has closed.  

(If no safety humidistat is used, skip this step.)  Open the 

AIR valve ONLY on one pair of heads.  There should be a 

constant flow of air from the heads with no flow of water.  

This will indicate that the controls for the control section 

are properly wired.  Make any corrections needed.  Close 

the air valve after determining wiring is correct.  Repeat 

the above at each control section in the system.

5.  CLEAN DISTRIBUTION LINES FROM CONTROL 

SECTIONS TO HEAD ASSEMBLIES.  

IMPORTANT: 

Be sure all air and water valves at head assemblies are 

closed (Step 2).  AIR LINES: Put on safety glasses.  With 

CONTROL humidistat ON and air valve at control section 

open, place bucket and cloth over hose bib at end of each 

air line and slowly open the hose bib and allow line to 

blow clean.  DO NOT LOOK INTO BUCKET WHILE AIR 

IS BLOWING.  Close hose bib.  Repeat on all air lines 

from each control section.  WATER LINES: (Air valve at 

control section should be open.)  Set SAFETY humidistat 

at maximum and CONTROL humidistat ON.  Open water 

valve at control section.  Place bucket or hose on ends 

of water lines and slowly open hose bibs.  Allow water to 

flow until clean.  Throttle valve to avoid splashing.  Close 

hose bib.  Close air and water valves at control section.  

Repeat on all water lines from each control section.

6.  STARTING THE SYSTEM.  

Close air and water valves 

at all control sections.  Open air valves only at all head 

assemblies.  Set humidistats high enough to assure 

system operation.  Open AIR valve at control section.  

With  air  flowing  through  heads,  adjust  primary  air 

pressure regulator (or compressor) to maintain 55 psi.  

Adjust control section air pressure regulator to 30 psi.  

With water valve open at water source, open the control 

section water valve and the water valve of the ONE 

head assembly located the GREATEST distance from 

the control section.  Adjust the primary water pressure 

reducer to provide 45-50 psi to the control section.  

Adjust control section water valve to provide 32-38 psi 

to heads.  Open the water valve at each head assembly, 

checking and correcting for air and water leaks as you 

go.  CAUTION: Never let water pressure get below 

air pressure as air will then get into water lines and 

necessitate bleeding of lines.  Repeat procedure on all 

control sections and primary reducers.  Normally, with all 

heads operating, it will be necessary to again adjust the 

primary water pressure reducer to 45-50 psi and control 

section water pressure regulator to 32-38 psi.  Tighten 

the locknut on all WATER pressure regulators - primary 

and control section.  All further adjustments will be made 

on air controls and at heads.  With the entire system in 

full operation, check for leaks in all air and water lines, 

fittings, connections, valves, control sections, and head 

assemblies.  Correct as required.

7.  FINAL ADJUSTMENTS TO HEADS.

  Remove cap 

(253206-00X) of each head.  This cap is at the non-

discharge end of the head and covers the head adjusting 

“spring tension nut” (253207-00X).  Slowly turn this 

adjusting nut in a clockwise direction until no water is 

discharged by the head.  Use care to avoid damage to 

the valve seat.  Then, back off this adjusting nut TWO full 

turns counter clockwise.  This may result in an excessively 

heavy spray, but this will be adjusted later in the control 

section.  Replace cap.  Repeat this operation on every 

head on the system.  NOTE: Maintain air pressure at 30 

psi and water pressure at 32 - 38 psi.  Do NOT let air 

pressure exceed water pressure.

8.  BALANCING THE SYSTEM.  

The  final  and  most 

important adjustment will be made at the air pressure 

regulator of each control section.  Adjust the air regulator 

to 30 psi; adjust water pressure for proper head capacity.  

Increasing the air pressure to the heads results in smaller 

droplet size in discharge pattern - and vice versa.  Spray 

pattern should be visible to at least 10’ from the head to 

assure rated capacity.  With the system in full operation, 

adjust the safety humidistat to 10% above the desired 

level.  Remove the cover of this humidistat and set the 

low and high limit stops to the RH setting so the setting 

cannot be changed.  Replace cover.  Move the CONTROL 

humidistat setting alternately lower and higher to cycle 

the system OFF and ON several times until all gauges 

become repetitive in action and readings.

Water Pressure Settings

Head Capacity

Water Pressure Setting (PSI)

6

32

8

38

10

33

12

35

15

37

Note:  A  new  system  may  require  some  adjustment  until  all  parts  are 

properly seated during break-in.  This period may last about two weeks.  

After that, adjustments may not be required but should be checked on a 

regular schedule.  Set the humidistat at the desired level.  

CAUTION: 

1.  Do not balance the system by adjusting individual heads.  Each 

head has been adjusted to provide its design capacity.

2.  Do not throttle any valves at control sections or head assemblies to 

get final adjustment.

VI. OPERATING INSTRUCTIONS

The Dual Pneumatic Atomizing System utilizes air and water 

under pressure to atomize the water into tiny droplets (2-

15 microns with an average of 7.5).  These droplets rapidly 

evaporate to a gaseous state to raise the level of relative 

humidity.

Содержание Heremidifier Dual Pneumatic

Страница 1: ...T R I O N w w w t r i o n i a q c o m Dual Pneumatic Atomizing System READ SAVE THESE INSTRUCTIONS...

Страница 2: ...matter must be flushed from air and water lines supplying the atomizing heads before the head valves are opened and heads used If foreign matter reaches the interior of the heads each head must be dis...

Страница 3: ...ncidental expenses such as cost of transporting the part unit to TRION shall be borne by the user Upon completion of the reconditioning the humidifier will be returned at no cost to the user In an eff...

Страница 4: ...se immediately preventing any chance of dripping or spitting At the end of each cycle the air pressure is allowed to fall gradually to zero through the heads blowing all water from the mixing chamber...

Страница 5: ...dard system consists of a control humidistat and high limit safety humidistat A hygrometer is optional with any Dual Pneumatic system For critical applications where extreme tolerances or temperature...

Страница 6: ...v i c e M a n u a l 6 www trioniaq com Figure 4 AH 1020 Air Control Section For System Capacities up to 240 lbs hr Approximate Measurements 23 L x 6 H Figure 5 AH 1050 Air Control Section For System C...

Страница 7: ...PRIMARY PRESSURE REGULATOR SECONDARY PRESSURE REGULATOR 1 2 NPT FEMALE DRAIN LOOP CONNECTION DRAIN LOOP MUST EXTEND MINIMUM OF 3 ABOVE ATOMIZING HEADS DRAIN LOOP SUPPLIED BY OTHER n THREE WAY WATER V...

Страница 8: ...ds in a manner where the spray will contact a wall machine unit heater pipes columns conveyer lights wires or obstructions Distance from such obstructions should not be less than the maximum visible s...

Страница 9: ...e height of the heads because the pressure readings at the control sections and heads will differ 3 Always be sure the drain from the 3 way solenoid extends a minimum of 3 above the heads pipe run or...

Страница 10: ...dure for the water line Clean lines to all control sections as described above 4 CHECK ELECTRICAL WIRING OF CONTROLS Set the SAFETY humidistat to maximum Set the CONTROL humidistat to 20 NOTE If only...

Страница 11: ...es and necessitate bleeding of lines Repeat procedure on all control sections and primary reducers Normally with all heads operating it will be necessary to again adjust the primary water pressure red...

Страница 12: ...ray pattern adequate At least ONCE A YEAR remove the atomizer nozzles AH 941 X X Clean these nozzles in a weak acid solution Do NOT use a wire or other object that will score the nozzle or its orifice...

Страница 13: ...quired Use a dependable psychrometer 3 Air and water valves serving the control section are not open 4 Electric current not flowing to central section Check wiring and supply lines 5 Compressed air is...

Страница 14: ...ell as the RH indicator with a dependable psychrometer and adjust as required 3 Be sure humidistat is not being influenced by a hot air stream blowing directly on it Correct as required EXCESSIVE AIR...

Страница 15: ...t 253208 001 Spring Nut 253208 002 Spring Nut AH 12 R Valve Stem w Needle AH 12 R SS Valve Stem w Needle AH 19A Air Port AH 19ASS Air Port AH 18A Union Tail Piece AH 18ASS Union Tail Piece AH 20 Union...

Страница 16: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 16 www trioniaq com X TYPICAL LAYOUTS...

Страница 17: ...Dual Pneumatic I n s t a l l a t i o n O p e r a t i o n S e r v i c e M a n u a l 17 www trioniaq com XI WIRING DIAGRAMS...

Страница 18: ...2018 TRION All Rights Reserved TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com Form No AH 22 Rev 06 18...

Отзывы: