- 14 -
‘
Installation
‘
‘
For Qualified HVAC Installer Only
‘
Location Selection
Remember to select a location that is readily accessible for periodic inspection and
cleaning of the Prefilters and Ionizing-Collecting Cells. Allow a minimum of 24” clearance
in front and 12” clearance above the air cleaner for component removal and service space.
Direction of Airflow through the Air Cleaner
Left to right airflow:
This air cleaner is factory set for left to right airflow when you are facing the Front Panel
Assembly.
Right to left airflow:
1. Remove the Prefilters and Ionizing-Collecting Cells from the cabinet. A plastic
positioning spacer is located inside the bottom of the cabinet. See illustration below.
This spacer is secured to the cabinet by a #6 Phillips Drive Screw to ensure installation
of the cells in the correct position with respect to airflow.
2. Remove the screw and reposition the spacer in the alternate hole in the bottom of the
cabinet.
3. Replace the screw to ensure the plastic spacer is not accidentally dislodged during
normal maintenance. The spacer must be installed in the hole provided nearest to the
air leaving side of the cabinet.
4. Remove the Ionizing-
Collecting Cell handle and re-
attach to the opposite end of
the cell(s). Turn Cells around,
(reversing their orientation)
and replace in cabinet. The
directional arrows on the Cell
end plates must point in the
direction of airflow. Reposition
Pre-filters on the air entering
side of the air cleaner.
- 11 -
‘
Installation
‘
‘
For Qualified HVAC Installer Only
‘
CAUTION:
The following section is to be used by a qualified HVAC Contractor / Installer ONLY.
These procedures are not to be attempted by any person not qualified to work with
high voltage or familiar with the installation of this type of air cleaner. Seller cannot
be help responsible for any injury or damage by any person not qualified to install
this product.
Technical Specifications
Model
HE Plus 1400
HE Plus 1400
HE Plus 2000
Dimensions
(nominal)
16” x 25” x 7”
20” x 20” x 7”
20” x 25” x 7”
Unit Part Number
120 V / 50-60 Hz
455600-125 455600-225 455600-025
Unit Part Number
240 V / 50-60 Hz
455600-126 455600-226 455600-026
Unit Part Number
240 V / 50-60 Hz
(European)
455600-127 455600-227 455600-027
Rated Airflow (max)
1400 CFM
(2380 m/hr)
1400 CFM
(2380 m/hr)
2000 CFM
(3400 m/hr)
Pressure Drop (max)
0.11” w.g.
@ 1400 CFM
0.11” w.g.
@ 1400 CFM
0.14” w.g.
@ 2000 CFM
Cell Weight
(2 cells in each unit)
10 lbs (4.5 kg) each
9 lbs (4.1 kg) each
12 lbs (5.5 kg) each
Unit Weight
32 lbs. (14.6 kg)
34 lbs. (15.5 kg)
36 lbs. (16.4 kg)
Power Consumption
(max)
40 watts
40 watts
48 watts
Electrical Output
2.5 MADC
@ 6200VDC
2.5 MADC
@ 6200VDC
3.2 MADC
@ 6200VDC
Classification
UL / CE
Accessories
(Optional)
Charcoal After Filter