- 14 - 

‘    

Installation 

  ‘ 

 ‘

   

For Qualified HVAC Installer Only

   

‘ 

 
 

Location Selection  

 
Remember to select a location that is readily accessible for periodic inspection and 
cleaning of the Prefilters and Ionizing-Collecting Cells.  Allow a minimum of 24” clearance 
in front and 12” clearance above the air cleaner for component removal and service space.  
 

Direction of Airflow through the Air Cleaner  
 
Left to right airflow:  
 

This air cleaner is factory set for left to right airflow when you are facing the Front Panel 
Assembly. 
 

Right to left airflow:  

 
1.   Remove the Prefilters and Ionizing-Collecting Cells from the cabinet.  A plastic 

positioning spacer is located inside the bottom of the cabinet.  See illustration below.  
This spacer is secured to the cabinet by a #6 Phillips Drive Screw to ensure installation 
of the cells in the correct position with respect to airflow.  

 
2.   Remove the screw and reposition the spacer in the alternate hole in the bottom of the 

cabinet.  

 
3.   Replace the screw to ensure the plastic spacer is not accidentally dislodged during 

normal maintenance.  The spacer must be installed in the hole provided nearest to the 
air leaving side of the cabinet. 

 
4.   Remove the Ionizing-

Collecting Cell handle and re-
attach to the opposite end of 
the cell(s). Turn Cells around,    
(reversing their orientation) 
and replace in cabinet.  The 
directional arrows on the Cell 
end plates must point in the 
direction of airflow.  Reposition 
Pre-filters on the air entering 
side of the air cleaner.    

 
 

- 11 - 

‘    

Installation 

  ‘ 

 ‘

   

For Qualified HVAC Installer Only

   

‘ 

 
 

CAUTION: 

The following section is to be used by a qualified HVAC Contractor / Installer ONLY.  
 
These procedures are not to be attempted by any person not qualified to work with 
high voltage or familiar with the installation of this type of air cleaner.  Seller cannot 
be help responsible for any injury or damage by any person not qualified to install 
this product.

 

 
 

Technical Specifications 

 

Model 

HE Plus 1400 

HE Plus 1400 

HE Plus 2000 

Dimensions 
(nominal) 

16” x 25” x 7” 

20” x 20” x 7”  

20” x 25” x 7” 

Unit Part Number  
 120 V / 50-60 Hz 

455600-125 455600-225 455600-025 

Unit Part Number 
  240 V / 50-60 Hz 

455600-126 455600-226 455600-026 

Unit Part Number 
  240 V / 50-60 Hz 
(European) 

455600-127 455600-227 455600-027 

Rated Airflow (max) 

1400 CFM 
 (2380 m/hr) 

1400 CFM  
(2380 m/hr) 

2000 CFM 
 (3400 m/hr) 

Pressure Drop (max) 

0.11” w.g.  
@ 1400 CFM 

0.11” w.g. 
 @ 1400 CFM 

0.14” w.g.  
@ 2000 CFM 

Cell Weight 
 (2 cells in each unit) 

10 lbs (4.5 kg) each 

 9 lbs (4.1 kg) each 

12 lbs (5.5 kg) each 

Unit Weight 

32 lbs. (14.6 kg) 

34 lbs. (15.5 kg) 

36 lbs. (16.4 kg) 

Power Consumption 
(max) 

40 watts 

40 watts 

48 watts 

Electrical Output 

2.5 MADC 
 @ 6200VDC 

2.5 MADC 
 @ 6200VDC 

3.2 MADC  
@ 6200VDC 

Classification 

UL / CE 

Accessories 
(Optional) 

Charcoal After Filter 

 

 

Содержание HE Plus 1400

Страница 1: ...02 customerservice trioniaq com 6 This limited warranty does not apply to any part or component that is damaged in transit or when handling has been subject to misuse neglect or accident has not been...

Страница 2: ...ts List REF NO DESCRIPTION HE PLUS 1400 16 x 25 HE PLUS 1400 20 x 20 HE PLUS 2000 20 x 25 1 Power Tray Assy 120 50 60 1 356066 0105 356066 0109 356066 0101 1A Power Tray Assy 240 50 60 1 356066 0116 3...

Страница 3: ...ulates including dust dirt smoke pollen virus spores bacteria and mold from indoor air Air movement through the unit is provided by the heating air conditioning or ventilating system blower As dirty a...

Страница 4: ...Air Cleaner Model Identification The model number and part number for your Electronic Air Cleaner can be found on the data label located on the inside of the Front Panel Assembly 23 Installation For...

Страница 5: ...new Electronic Air Cleaner will efficiently clean and filter your household air It will not eliminate the need for regular dusting of your furniture and belongings Duct mounted air cleaners can only c...

Страница 6: ...be located by checking operation of the safety interlock switch and the interconnecting wiring with a Multimeter Refer to Circuit Diagram page 22 to check operation of the switches Primary Circuit wi...

Страница 7: ...ons More frequent washing once every one to three months may be necessary with some installations new home for example where there is new carpeting plaster dust or excessive cigarette smoke CAUTION Ha...

Страница 8: ...g alcohol and carefully insert into the 3 16 diameter hole located in the front right hand side of the Power Tray Assembly when facing the unit Carefully twirl the cotton swab between your fingers mak...

Страница 9: ...so that the air movement will carry the dirt to the air cleaner where it can be collected Unfortunately there will always be some dirt that is left behind on the appliances furniture etc Regular dust...

Страница 10: ...usage of the HVAC system blower will depend on the age and size of your system energy costs in your regional location and other variables The best solution is to operate the HVAC system blower in a c...

Страница 11: ...ting with a variety of furnace installations continued on next page 9 Troubleshooting Common Troubleshooting Techniques Symptom Possible Causes Corrective Action Rapid Arcing or Zapping Broken or loos...

Страница 12: ...1 21 3 8 543 7 1 8 181 MODEL DIM E DIM F DIM G inches mm inches mm inches mm HE PLUS 2000 17 7 8 454 22 1 2 572 21 7 16 545 HE PLUS 1400 13 7 8 352 22 1 2 572 21 7 16 545 HE PLUS 20 X 20 17 7 8 454 19...

Страница 13: ...Turn Cells around reversing their orientation and replace in cabinet The directional arrows on the Cell end plates must point in the direction of airflow Reposition Pre filters on the air entering sid...

Страница 14: ...ir cleaner s efficiency and reduce the life of the high voltage power supply Evaporative Humidifiers An evaporative type humidifier can be mounted either upstream or downstream of the air cleaner depe...

Отзывы: