www.trioniaq.com
Grease Viper
11
I n s t a l l a t i o n , O p e r a t i o n , a n d S e r v i c e M a n u a l
Ionizing-Collecting Cell(s) - Every 6 Months
Handle cells with care to avoid damage to the
insulators and especially the brass contact plungers.
Remove and inspect the ionizing-collecting cells for
excessive contaminant accumulations not removed
by the integral washing system. Manually clean as
required in a soak tank, commercial car wash, or
with a pressure hose or pressure cleaner using a low
pressure setting. At this time, particular care should
be taken in cleaning each of the insulators.
Odor Control Panels - Every 6 Months
Replace or refill panels with odor adsorber granules,
as required.
Motors – Every 24 Months
As the operation of detergent pump motor is limited, fre-
quent oiling is not required. Lubricate with several drops
of SAE 10 motor oil every two years. DO NOT OVER
OIL. Lubricate fan motor per manufacturer’s guidelines.
Filter Devices – Every 4 to 6 Months
Hoods, impingers, metal mesh filters, ducts, and other
appurtenances shall be cleaned to bare metal at
frequent intervals prior to surfaces becoming heavily
contaminated with grease, oil or other contaminant.
It may be advantageous to clean readily removable
items, such as impingers, metal mesh filters or other
permanent filter devices in a soak tank, with a pressure
hose or pressure cleaner using a low pressure setting.
After cleaning to bare metal, components shall not be
coated with powder or other substance. Allow filters to
completely air dry before installing in cabinet.
When a cleaning service is used, a certificate showing
dates of inspection and/or cleaning shall be maintained
on the premises.
WARNING
RISK OF ELECTRIC SHOCK
These servicing instructions are for use by
qualified personnel only. To reduce the risk of
electric shock, do not perform any servicing other
than that contained in the operating instructions
unless you are qualified to do so.
NOTE
All repairs to the fire suppression system (if
supplied) must be completed by the authorized
fire control contractor.
At the start of the cleaning process, electrical switches
that could be accidentally activated shall be locked
out. Components of the fire suppression system (if
installed) shall not be rendered inoperable during the
cleaning process.
Care should be taken not to apply cleaning chemicals
on any fusible links or other detection devices of the
automatic extinguishing system.
7. Troubleshooting
Introduction
This section on troubleshooting provides a description
of potential malfunctions, their cause, location and
correction. A Troubleshooting Reference Chart listing
the most probable causes and corrections follows the
general text.
WARNING
RISK OF ELECTRIC SHOCK
These servicing instructions are for use by
qualified personnel only. To reduce the risk of
electric shock, do not perform any servicing other
than that contained in the operating instructions
unless you are qualified to do so.
WARNING
Flammable solvents or other flammable cleaning
aids shall not be used.
WARNING
EXERCISE THE USUAL PRECAUTIONS
WHEN WORKING WITH HIGH VOLTAGE. THE
MAXIMUM OPERATING OUTPUT FROM THE
POWER SUPPLY IS 12,000 VDC AND 8 MA
WITH TWO POWER SUPPLIES IN PARALLEL.
IF SAFETY SWITCHES ARE CLOSED AND
CIRCUIT IS ENERGIZED, DO NOT TOUCH
HIGH VOLTAGE. WHEN THE CIRCUIT IS
DE-ENERGIZED, ALWAYS BLEED OFF
REMAINING STATIC CHARGE WITH AN
INSULATED HANDLED SCREW DRIVER BY
SHORTING TO GROUND THE POINTS OF
HIGH VOLTAGE DC POTENTIAL.