background image

www.trioniaq.com

Grease Viper

10

I n s t a l l a t i o n ,   O p e r a t i o n ,   &   S e r v i c e   M a n u a l

others and require a stronger detergent solution. 

Average settings have been factory set. Best possible 

settings for any given installation, however, are 

determined through experience. Determination can be 

made by visually examining the collecting elements 

after the first few wash cycles. 

To adjust the volume of detergent used within the given 

time setting, loosen the knurled knob with an Allen 

wrench on the control valve located in the by-pass 

line. Refer to the Detergent System Outline. Turning 

the knob clockwise increases the volume and counter 

clockwise decreases the volume. When adjustment 

has been made, be sure to retighten the setscrew.

5.   Routine Maintenance

Washing Frequency

The frequency that the collected contaminant is 

to be washed from the unit depends upon the type 

and amount of contaminant in the air to be cleaned. 

Contaminant which is greasy in nature tends to 

harden after collection and should be washed away 

often. Likewise, units operating under extremely 

heavy contaminant loads should be washed more 

often as a large build-up of collected material will have 

a tendency to “blow-off” if permitted to remain on the 

collecting elements for long periods of time. In that the 

type and amount of contaminant varies geographically 

(and from one location to another in any given area) 

it is recommended to start operation with a washing 

frequency of at least once a week. This schedule may 

then be altered as needed after visual examinations 

of the collected material contained on the ionizing-

collecting cells. Daily washing is not unusual for units 

operating on heavy welding fume, kitchen exhaust 

hoods or similar applications. Start time programming 

is recommended to be within one hour of the end of 

cooking time.

Detergent

Effective washing is dependent upon detergent. The 

detergent reservoir should be examined on a routine 

basis, a minimum tank level established, and never 

permitted to empty. An empty tank not only means poor 

washing, but can also be detrimental to the pump. The 

inside of the tank should be kept clean, free from dirt and 

foreign objects. The detergent, as supplied by TRION

®

is formulated specifically for electronic air cleaners.  If 

substitutes are used, they must be approved by TRION

®

so as to not void the warranty. They should be safe for 

use  in  ventilation  systems  and  non-caustic,  as  95%  of 

the ionizing-collecting cells are constructed of aluminum, 

special high voltage insulation and gasket seals.

Electrical Operation

The ESP section(s) access doors have LED indicating 

lights to show status of the power supplies. Illumination

of LED(s) indicates proper operation. Flickering or dim 

LED(s) indicate arcing within the ionizing-collecting 

cell(s). No illumination indicates lack of input power, 

dead short in ionizing-collecting cell(s), failed power 

supply, and/or failed LED.

6.   Periodic Maintenance

Water Wash System - Every 6 Months

The water wash spray pattern should be checked 

on each nozzle to be sure that a full spray pattern is 

developed. Distorted patterns are usually caused by 

contaminant in the nozzle orifice, which can be cleaned 

by inserting a small gage, soft copper wire into the 

orifice.  If  any  one  manifold  contains  several  nozzles 

that are restricted, remove the manifold and thoroughly 

flush. The main supply line strainer and the strainer in 

the detergent system should be checked and cleaned.

Fire Suppression System (IF INSTALLED) - Every 

6 Months

Properly  trained  and  qualified  personnel  shall 

complete inspection, cleaning and servicing of the fire 

suppression system.

All actuation components, including remote manual pull 

stations, mechanical or electrical devices, detectors, 

fire-actuated  dampers,  etc.,  shall  be  checked  for 

proper operation in accordance with the manufacturers 

listed procedures. In addition to these requirements, 

the specific inspection requirements of the applicable 

NFPA standard shall also be followed. If required, 

certificates  of  inspection  and  maintenance  shall  be 

forwarded to the authority having jurisdiction.

Control Panel - Every 12 Months

The inside of the controller cabinet should be 

examined for accumulated dirt and dust. If required, 

the components should be cleaned using a good brand 

of electrical contact cleaner. All terminal connections 

approved should be checked for securement and 

tightened or reworked as required.

Содержание Grease Viper Series

Страница 1: ...T R I O N w w w t r i o n i a q c o m Grease Viper Series Electrostatic Precipitators Commercial Industrial Applications READ AND SAVE THESE INSTRUCTIONS ...

Страница 2: ...or 1 Unpack and Inspect 4 2 Position Air Cleaner Cabinet 5 3 Connect Adjoining Ductwork 5 4 MountDetergentSystem 5 5 Connect Drain 5 6 Connect Water Wash Supply 5 7 MountControlPanel 6 8 Complete Wiring a Primary Wiring 6 b Grounding 6 9 Checkout for System Start up 6 Section 3 Operation Service For the Maintenance Engineer 1 Introduction and Principle of Operation 6 2 General Description 7 3 Init...

Страница 3: ...reactivated carbon Gasketed access doors located on one side of the cabinet 90 degrees to the direction of the airflow provide entry for removal of the cells and filters The location of the access doors may be specified as right hand or left hand access determined by facing the inlet of the ESP dirty airflow at your back The solid state high voltage power supplies are factory installed and wired w...

Страница 4: ...nit and detergent system Where applicable all water lines must be protected from freezing SAFETY NOTE Factory designed access to all electrically charged high voltage components contain electrical interlocks for the safety of operating personnel Any additional access that may be provided in the system where there is access to high voltage must be equipped with such interlocks Interlocks are readil...

Страница 5: ... pan supply through the floor The recommended drain line trap to seal off the cabinet from the drain against the system pressure and the drain dump valve should be located in the heated interior If not installed in this manner heat trace or other means should be employed to prevent freezing Clean outs are recommended to be installed in all drain lines Wash Water Supply Line The length of the wash ...

Страница 6: ...emperatures must be considered see detailed Warning on Page 6 cabinet then re install the ionizing collecting cells and all other filters When the ionizing collecting cells are reinstalled the directional arrows on the cell end plates must concur with airflow direction through the cabinet Impinger prefilters are to be installed within the inlet plenum section on the air entering side of the unit 4...

Страница 7: ...n accordance with the plumbing schematic to prevent freezing 2 All piping exposed to cold climate outdoor conditions should be heat traced and insulated to prevent freezing 3 An air gap fitting should be installed on the drain line to facilitate gravity draining of wash water from the internal headers and manifolds 4 The water supply line should be pitched back toward the heated space 9 Check Out ...

Страница 8: ...s On multi cell units all of the electrical connections between cells in a given tier are automatically made through spring plunger connectors Install cells into the cabinet in accordance with the directional arrows on the cell end plates The side of the cell containing the spiked ionizer blades must always be located on the air entering side The spring plunger connectors located on one end of eac...

Страница 9: ...in the drain basin for any restrictions The ducting where secured to the cabinet collars should be sealed water tight either with gasketing or caulking 2 Inspect the ionizing collecting cells to see that all of the ionizing blades are intact that no large pieces of foreign material are lodged between the plates and that the cells are properly installed in the cabinet with the spiked ionizing blade...

Страница 10: ...ion is only effective when timer is running in AUTO mode Temporary Override Condition 1 When timer s output status is ON press MANUAL key to move indicator from AUTO to OFF Timer output shall turn to OFF status programs overrided Press MANUAL again to switch timer status to AUTO Timer s output shall continue maintaining OFF Timer shall resume its automatic operation when next program event calls f...

Страница 11: ...he inside of the tank should be kept clean free from dirt and foreign objects The detergent as supplied by TRION is formulated specifically for electronic air cleaners If substitutes are used they must be approved by TRION so as to not void the warranty They should be safe for use in ventilation systems and non caustic as 95 of the ionizing collecting cells are constructed of aluminum special high...

Страница 12: ... or cleaning shall be maintained on the premises WARNING RISK OF ELECTRIC SHOCK These servicing instructions are for use by qualified personnel only To reduce the risk of electric shock do not perform any servicing other than that contained in the operating instructions unless you are qualified to do so NOTE All repairs to the fire suppression system if supplied must be completed by the authorized...

Страница 13: ...h voltage power supply s is 12 000 VDC and up to 8 MA When the power supply s is de energized there is a 20 second delay for the voltage to decay Always short from ground to a point of high voltage with a well insulated jumper wire or an insulated handled screwdriver to bleed off any remaining residual charge NOTE It will be necessary to close the access door electrical interlock switch operated b...

Страница 14: ... indicating light Replace light d Malfunctions other than short or open circuits refer to the Troubleshooting Reference Chart below Problem Symptom Probable Cause Location Reason Correction Indicating Light Not Glowing Short Circuit Ionizing Section of Cell 1 Dirty Insulator s Clean 2 Defective Insulator s Replace 3 Foreign Object between Spiked Ionizer and Ground Electrode Remove Collecting Secti...

Страница 15: ...on and Buyer s sole and exclusive remedy for any breach of this warranty repair or replace reperform the Goods which gave rise to the breach or at Seller option refund the amounts paid by Buyer for the Goods which gave rise to the breach Any repair replacement or reperformance by Seller hereunder shall not extend the applicable Warranty Period The parties shall mutually agree on the specifications...

Страница 16: ...TRION 101 McNeill Rd Sanford NC 27330 P 800 884 0002 F 800 458 2379 www trioniaq com customerservice trioniaq com TRION 2017 All Rights Reserved Form No 266206 001 Rev 09 17 ...

Отзывы: